Enumeration | Original | A | 8/15/2025 | BRENT | BRENT | | | Enumeration | 2198290 |
Electronic Plan | Original | / | 8/15/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2198279 |
Submittal 2 | Original | / | 8/15/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2198150 |
Cherokee Water | Original | D | 8/5/2025 | CHEROKEEMETRO | CHEROKEEMETRO | Add the Cherokee Meter installation schematic to plan under plumbing or with the "Utility Service Plan" sheets. Utility Service plans can be pulled from the "site development plan" from the EDARP File number PPR2445; add those to this Plan. You can email bzembles@cherokeemetro.org for these schematics also | bzembles | Cherokee Water | 2194058 |
Cherokee Waste Water | Original | D | 8/5/2025 | CHEROKEEMETRO | CHEROKEEMETRO | Include a schematic of the 1500-gal grease interceptor. Additionally, add the approved "Utility Service Plan" sheets from the "site development plan" from the EDARP File number PPR2445 to this Plan. | bzembles | Cherokee Waste Water | 2194051 |
EPC Health Dept | Original | A | 8/1/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. BR | brothrock | EPC Health Dept | 2192495 |
Cimarron Hills Hazmat | Original | N | 7/28/2025 | CHFIRE | CHFIRE | Not Applicable Thomas P Joyce Fire Inspector III / Plans Examiner | tjoyce@cimarronhills | Cimarron Hills Hazmat | 2190088 |
Cimarron Hills Fire | Original | A | 7/28/2025 | CHFIRE | CHFIRE | CHFD has reviewed and approved the fire and life safety plans for Chipotle Mexican Grill, 7351 Central Rail Point. Thomas P Joyce Fire Inspector III / Plans Examiner | tjoyce@cimarronhills | Cimarron Hills Fire | 2190087 |
Energy | Original | D | 7/25/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2189171 |
Electrical | Original | D | 7/25/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2189170 |
Electronic Plan | Original | / | 7/25/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2189167 |
Mechanical | Original | D | 7/24/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Provide manufacturers hood sheets * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2189048 |
Plumbing | Original | D | 7/24/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview All gas piping and condensate piping related items shall be on the mechanical plans. Remove ALL references to gas and condensate piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Three compartment sink detail does not comply with section 802.1.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2188787 |
County Zoning | Original | D | 7/24/2025 | DSDDEAN2 | DSDDEAN2 | Site Development Plan at PCD Fil No PPR2445 was approved on 6/19/2025. Please upload the stamped approved Site Development Plan with these plans, as uploaded to EDARP in the "Approved Documents" section. | | County Zoning | 2188742 |
Zoning/Planning | Original | / | 7/24/2025 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2188706 |
EPC Health Dept | Original | D | 7/23/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2188458 |
Construction | Original | D | 7/23/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2188334 |
Electronic Plan | Original | / | 7/22/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2187320 |
Enumeration | Original | A | 7/21/2025 | BRENT | BRENT | | | Enumeration | 2187160 |
Electronic Plan | Original | / | 7/21/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2187154 |
Fire | Original | / | 7/21/2025 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2186880 |
Hazmat | Original | / | 7/21/2025 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2186879 |
Energy | Original | / | 7/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2186878 |
Floodplain | Original | N | 7/21/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5408305008) | | Floodplain | 2186876 |