Cherokee Water | Original | D | 9/3/2025 | CHEROKEEMETRO | CHEROKEEMETRO | Sheet U1.1 shows the proposed 1.5 DW and 4" fire line which are acceptable, but the plumbing plans do not show the new water lines connecting to existing internal piping | bzembles | Cherokee Water | 2206365 |
Cherokee Waste Water | Original | D | 9/3/2025 | CHEROKEEMETRO | CHEROKEEMETRO | See notes on plumbing and utility plans specifying sanitary lines going into Sand/oil separator and which are bypassing to include the new outdoor kitchen area | bzembles | Cherokee Waste Water | 2206361 |
Energy | Original | D | 8/22/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2201223 |
Electrical | Original | D | 8/22/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2201222 |
Electronic Plan | Original | / | 8/22/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2201203 |
Mechanical | Original | D | 8/20/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2200002 |
County Zoning | Original | D | 8/14/2025 | DSDDEAN2 | DSDDEAN2 | Applicant has not submitted for their Approval of Location project or their COM project to add covered parking and change the curb cuts yet. They were sent submittal requests from Planning and Community Development on 8/13/2025. | | County Zoning | 2197478 |
Zoning/Planning | Original | / | 8/14/2025 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2197281 |
Plumbing | Original | D | 8/13/2025 | SHANEN | SHANEN | Provide required water pipe size analysis data, see 2021 IPC appendix E. Provide WH-1 performance efficiency. EWC does not comply with section 410.3. 2"FD1 does not comply with section 413.4. 3/4"DCW is undersized to serve downstream fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2197213 |
Construction | Original | D | 8/13/2025 | BPHILLIPS | BPHILLIPS | Accessibility plan, life safety plan, Type B requirements * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2197187 |
Electronic Plan | Original | / | 8/12/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2196466 |
Enumeration | Original | N | 8/7/2025 | BECKYA | BECKYA | | | Enumeration | 2194898 |
Electronic Plan | Original | / | 8/7/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2194889 |
Fire | Original | / | 8/7/2025 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2194722 |
Hazmat | Original | / | 8/7/2025 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2194721 |
Energy | Original | / | 8/7/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2194720 |
Floodplain | Original | N | 8/7/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5407202012) | | Floodplain | 2194719 |