CO Springs DRE | Original | A | 10/9/2025 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2222220 |
Energy | Original | D | 10/9/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2221591 |
Electrical | Original | D | 10/9/2025 | BERTHA | BERTHA | Comply with 250.122 NEC
Provide location of new service disconnect on site plan. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2221590 |
Electronic Plan | Original | / | 10/8/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2221448 |
Mechanical | Original | D | 10/8/2025 | DALEH | DALEH | Waiting on construction comments being addressed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2221271 |
Zoning/Planning | Original | / | 10/8/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2221200 |
Plumbing | Original | D | 10/8/2025 | SHANEN | SHANEN | Construction review comments must be addressed. Drinking fountain (BF-1?) does not comply with section 410.3. Provide sheet P-501 and P-601. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2221174 |
Construction | Original | D | 10/8/2025 | DOUGC | DOUGC | Accessibility // Floor Plan // Pool Infill * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2221164 |
Electronic Plan | Original | / | 10/8/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2221096 |
| Original | / | 10/8/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2220922 |
| Original | / | 9/26/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2216380 |
Submittal 3 | Original | / | 9/26/2025 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2216379 |
CO Springs Fire | Original | D | 9/24/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2215118 |
CO Springs DRE | Original | A | 9/16/2025 | SSADLER | SSADLER | Interior remodel only. No change in footprint, No change in parking. No change in occupancy. | | CO Springs DRE | 2211358 |
Electrical | Original | D | 9/15/2025 | BERTHA | BERTHA | Comply with previous review comment - Remove parallel neutral - remove equipment ground from service conductor.
Comply with 250.24(A)(1) - NEC
Pending Construction review - see Construction review comments. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2210688 |
Energy | Original | D | 9/15/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2210689 |
Electronic Plan | Original | / | 9/12/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2210524 |
Plumbing | Original | D | 9/11/2025 | SHANEN | SHANEN | P-000: Construction review comments regarding scope of project must be addressed to verify compliance with section 403.1. P-601: Change of occupancy will require compliance with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2209714 |
Mechanical | Original | D | 9/11/2025 | DALEH | DALEH | Need construction type prior to mechanical * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2209397 |
Zoning/Planning | Original | / | 9/10/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2209195 |
Construction | Original | D | 9/10/2025 | DOUGC | DOUGC | Type of construction // Accessibility // Rated assemblies * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2209122 |
Electronic Plan | Original | / | 9/9/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2208666 |
Submittal 2 | Original | / | 9/9/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2208619 |
Energy | Original | D | 8/24/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2201665 |
Electrical | Original | D | 8/24/2025 | BERTHA | BERTHA | Remove parallel neutral - remove equipment ground from service conductor.
Provide compliance with 250.66
Clarify rating for Panel A - 200A on one-line and panel schedule vs 100A in Load Summary.
Provide available fault current at Panel A
Provide room names on plans
Lighting controls must be clearly shown and must comply with C405.2 (Interior) - 2021 IECC
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4 - 2021 IECC
Pending Construction review - see Construction review comments. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2201664 |
Electronic Plan | Original | / | 8/24/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2201663 |
CO Springs Hazmat | Original | N | 8/21/2025 | CSFIRE | CSFIRE | No inspection | michael.davis1@color | CO Springs Hazmat | 2200669 |
CO Springs Fire | Original | D | 8/21/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2200652 |
CO Springs DRE | Original | D | 8/18/2025 | SSADLER | SSADLER | On the code study form, list the current use of the space and the proposed use. | | CO Springs DRE | 2198990 |
Mechanical | Original | D | 8/18/2025 | DALEH | DALEH | See construction plan review comments Provide revised mechanical sheets as needed No review * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2198530 |
Plumbing | Original | D | 8/15/2025 | SHANEN | SHANEN | P-000: Construction review comments regarding scope of project must be addressed to verify compliance with section 403.1. P-501: Show existing expansion device location to verify compliance with section 607.3. P-601: Change of occupancy will require compliance with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2197838 |
Electronic Plan | Original | / | 8/15/2025 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2197830 |
CSU Water | Original | N | 8/14/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2197721 |
Zoning/Planning | Original | / | 8/14/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2197719 |
CSU Waste Water | Original | N | 8/14/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2197717 |
Energy | Original | / | 8/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2197710 |
Construction | Original | D | 8/14/2025 | DOUGC | DOUGC | Preliminary review only * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2197707 |
Electronic Plan | Original | / | 8/14/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2197576 |
Enumeration | Original | N | 8/11/2025 | BECKYA | BECKYA | | | Enumeration | 2195672 |
Electronic Plan | Original | / | 8/11/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2195666 |
Energy | Original | / | 8/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2195445 |
Floodplain | Original | N | 8/8/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6427307015) | | Floodplain | 2195444 |