EPC Health Dept | Original | N | 9/5/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. Change of occupancy (dodgeball, playground area, and trampoline). MT | mtemple | EPC Health Dept | 2207462 |
CO Springs Fire | Original | D | 9/3/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2206569 |
CO Springs Hazmat | Original | D | 9/3/2025 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2206568 |
Electrical | Original | D | 9/2/2025 | BERTHA | BERTHA | Provide one-line, include all conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide calculated load of service
Provide footprint (site plan) showing all electrical service equipment and disconnects serving the structure
Provide electrical plans with room names on them.
Lighting controls must be clearly shown and must comply with C405.2 - 2021 IECC
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Complete re-review . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2205865 |
Energy | Original | D | 9/2/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2205866 |
Electronic Plan | Original | / | 9/2/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2205731 |
CO Springs DRE | Original | D | 8/29/2025 | SSADLER | SSADLER | On the site plan, list the current use. There may be fees owed for business change. | | CO Springs DRE | 2205093 |
Mechanical | Original | D | 8/28/2025 | TREVORH | TREVORH | Disapproved; Mechanical plan submittal has to many items to list see link. www.pprbd.org/File/ByAlias/CommercialChangeOfOccupancy * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2204978 |
CSU Water | Original | N | 8/27/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2204280 |
CSU Waste Water | Original | N | 8/27/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2204279 |
Zoning/Planning | Original | / | 8/27/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2203793 |
Plumbing | Original | D | 8/26/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview Show water distribution piping. Show location of and piping for the indicated and scheduled mop sink. Provided water pipe size analysis data is incomplete. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2203711 |
Construction | Original | D | 8/26/2025 | JUSTINL | JUSTINL | See code study and architectural sheets for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2203675 |
Electronic Plan | Original | / | 8/26/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2203361 |
Enumeration | Original | N | 8/26/2025 | AMY | AMY | | | Enumeration | 2203354 |
Enumeration | Original | N | 8/26/2025 | AMY | AMY | | | Enumeration | 2203335 |
Electronic Plan | Original | / | 8/26/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2203325 |
Energy | Original | / | 8/15/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2198349 |
Floodplain | Original | N | 8/15/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6305101001) | | Floodplain | 2198348 |