Woodmoor Water | Original | D | 9/23/2025 | WOODWATER | WOODWATER | Please see all WWSD Comments on the Reviewed Progress Set for all comments related to the proposed water and sewer. | wwsdengineer | Woodmoor Water | 2214862 |
Woodmoor Waste Water | Original | D | 9/23/2025 | WOODWATER | WOODWATER | Please see all WWSD Comments on the Reviewed progress set for all comments related to the proposed water and sewer. | wwsdengineer | Woodmoor Waste Water | 2214856 |
Electrical | Original | D | 9/8/2025 | BERTHA | BERTHA | Comply with Core Electric Cooperative standards - EUSERC requirement.
Provide elevator horsepower on the one line.
Provide elevator feeder size, type, and quantity on the one line.
Provide elevator over current device size ( Ampacity) on the one line.
Pending approval in Elevators - see elevator review comments.
Comply with 445.19(B) NEC
Comply with 210.12(D) NEC
Provide a cord reel detail - comply with 314.23(H)
Requirements for compliance with 2021 IECC
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Remove all T sheets - provide Electrical sheets only .
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2208080 |
Energy | Original | D | 9/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2208081 |
Mechanical | Original | D | 9/8/2025 | TCRIPPEN | TCRIPPEN | Disapproved: See pages * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2207649 |
Plumbing | Original | D | 9/4/2025 | SHANEN | SHANEN | Preliminary review. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to uniform codes. Construction review comments regarding occupancy/occupant load must be addressed to verify compliance with section 403. Reference the rainfall map for the western US. Building orientation does not match architectural or utility plans. Water service and fire line locations do not match the utility plan. Clarify how the sanitary sewer is protected from kitchen area fixtures that might discharge fats, oils or grease (FOG) to the building drain. A grease interceptor may be required. Elevator sump discharge must show compliance with section 301.6. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Provide a piping materials schedule on the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2206763 |
Electronic Plan | Original | / | 9/3/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2206556 |
Elevators | Original | D | 9/3/2025 | ROBERTV | ROBERTV | Need site specific shop drawings and power data for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved. Also see sheets: A410, M-101, E-101, E-102, P-100. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2206527 |
Monument Zoning | Original | D | 8/28/2025 | TOWNOFMON | TOWNOFMON | Site Plan CD's still being reviewed by the Town of Monument. | bholtztom | Monument Zoning | 2205012 |
Tri-Lakes Hazmat (CSFD) | Original | N | 8/28/2025 | CSFIRE | CSFIRE | | phil.valdez | Tri-Lakes Hazmat (CSFD) | 2204626 |
Tri-Lakes Fire (CSFD) | Original | D | 8/28/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | Tri-Lakes Fire (CSFD) | 2204625 |
Gas/Elec. Utils | Original | D | 8/26/2025 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities gas/electric service territory. DMM | dmakings | Gas/Elec. Utils | 2203322 |
CSU Contract Admin. | Original | D | 8/25/2025 | CSUAPPSPRM | CSUAPPSPRM | Not within Colorado Springs Utilities service territory - no development charges and fees paid to CSU - MKL | mkluke | CSU Contract Admin. | 2201815 |
EPC Health Dept | Original | N | 8/22/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. TG | tguerrero | EPC Health Dept | 2201608 |
Construction | Original | D | 8/22/2025 | JUSTINL | JUSTINL | Preliminary review only. Conflicting information on plans. See life safety plan, architectural, IECC documents for preliminary review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2201605 |
Energy | Original | / | 8/22/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2201604 |
Electronic Plan | Original | / | 8/21/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2200832 |
Enumeration | Original | D | 8/19/2025 | BRENT | BRENT | Enumerations has not yet received a copy of the final recorded plat for Woodmoor Placer Replat B Subdivision. Enumerations approval pending receipt in our office of a copy of the final recorded plat.l * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2199475 |
Floodplain | Original | N | 8/19/2025 | BRENT | BRENT | | | Floodplain | 2199471 |
Electronic Plan | Original | / | 8/19/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2199452 |
Fire | Original | / | 8/18/2025 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2198954 |
Waste Water Div | Original | / | 8/18/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2198955 |
Hazmat | Original | / | 8/18/2025 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2198953 |
Energy | Original | / | 8/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2198952 |