Plan #
  
Type
 
Plan
Owner
Address
2 PENROSE BLVD, COLORADO SPRINGS, CO 80906
Parcel Info
7435409003
Truss P/SF
30 (Elevation: 6,339 Feet)
Project
COMMERCIAL CHANGE OF OCCUPANCY (
542
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
COLORADO SPRINGS FIRE DIST
Submit Date
Approval Date
Location
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 14
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Construction
D
0
C
Construction
Electrical
/
E
Electrical
Elevators
D
0
X
Elevators
Energy
/
G
Energy
Enumeration
N
0
N
Enumeration
CO Springs Fire
/
F
CO Springs Fire
Floodplain
N
W
Floodplain
CO Springs Hazmat
/
B
CO Springs Hazmat
EPC Health Dept
N
H
EPC Health Dept
Mechanical
/
M
Mechanical
Plumbing
D
0
P
Plumbing
CSU Waste Water
N
Y
CSU Waste Water
CSU Water
N
A
CSU Water
CO Springs DRE
D
0
Z
CO Springs DRE
Log Entries: 14
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
CO Springs DRE
Original
D
9/12/2025
SSADLER
SSADLER
Once the modification to the development plan is approved, upload the approved and stamped plans and the approval letter.
CO Springs DRE
2210103
Plumbing
Original
D
9/10/2025
SHANEN
SHANEN
Preliminary review. P001: Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. P123: Provide gpm and/or square footage served by each component of the roof drainage system. P610: Provide required water pipe size analysis data, see 2021 IPC appendix E.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Plumbing
2208982
EPC Health Dept
Original
N
9/10/2025
HEALTHDEPT
HEALTHDEPT
Not applicable. Warming kitchen for use by licensed caterers only. BR
brothrock
EPC Health Dept
2208830
Elevators
Original
D
9/9/2025
ROBERTV
ROBERTV
See Sheet A610: Need site specific shop drawings and power data for ADA lift being installed. All ADA lift drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
See Sheet A300: What is being done with the existing elevator besides smoke curtains ?
.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Elevators
2208462
Zoning/Planning
Original
/
9/9/2025
SSADLER
SSADLER
In Current Review by SSADLER
Zoning/Planning
2208179
CSU Water
Original
N
9/8/2025
CSUREVIEW
CSUREVIEW
No new water service outside of building. DMM
dmakings
CSU Water
2208049
CSU Waste Water
Original
N
9/8/2025
CSUREVIEW
CSUREVIEW
No new wastewater service outside of building. DMM
dmakings
CSU Waste Water
2208048
Construction
Original
D
9/8/2025
JUSTINL
JUSTINL
See code study form, architectural and structural sheets for review comments.
Missing IECC document.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Construction
2207891
Energy
Original
/
9/8/2025
SYSTEM
SYSTEM
Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews
Energy
2207746
Electronic Plan
Original
/
8/29/2025
JUSTINL
JUSTINL
In Current Review by JUSTINL
Electronic Plan
2205373
Enumeration
Original
N
8/27/2025
AMY
AMY
Enumeration
2204100
Electronic Plan
Original
/
8/27/2025
AMY
AMY
In Current Review by AMY
Electronic Plan
2204071
Energy
Original
/
8/26/2025
SYSTEM
SYSTEM
Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews
Energy
2203422
Floodplain
Original
N
8/26/2025
RBD GIS
RBD GIS
Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7435409002)
Floodplain
2203420