| Falcon Fire (CSFD) | Original | D | 10/1/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | Falcon Fire (CSFD) | 2366181 |
| Falcon Hazmat (CSFD) | Original | D | 10/1/2026 | CSFIRE | CSFIRE | | chiptaylor | Falcon Hazmat (CSFD) | 2366178 |
| Meridian Ranch Water | Original | A | 9/29/2026 | MERIDIANRANCH | MERIDIANRANCH | | LawrenceGrahem | Meridian Ranch Water | 2364628 |
| Energy | Original | D | 9/29/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2364617 |
| Mechanical | Original | D | 9/29/2026 | TCRIPPEN | TCRIPPEN | Disapproved:Remove this note, Or add walk in cooler to this plan show locations Or provide new plan page as splice * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2364616 |
| Meridian Ranch Waste Water | Original | A | 9/29/2026 | MERIDIANRANCH | MERIDIANRANCH | | LawrenceGrahem | Meridian Ranch Waste Water | 2364613 |
| EPC Health Dept | Original | D | 9/23/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3.GGM | Heagmiranda | EPC Health Dept | 2363003 |
| County Zoning | Original | N | 9/23/2026 | DSDRANGEL | DSDRANGEL | | | County Zoning | 2362876 |
| Zoning/Planning | Original | / | 9/23/2026 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 2362875 |
| Gas/Elec. Utils | Original | A | 9/23/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts. | nferguson | Gas/Elec. Utils | 2362838 |
| Electrical | Original | D | 9/23/2026 | DANIELG | DANIELG | Add the load for the new CU 1,2,3 and Evap to the panel schedule. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2362738 |
| Electronic Plan | Original | / | 9/23/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2362732 |
| Plumbing | Original | D | 9/23/2026 | SHANEN | SHANEN | EWC-1 does not comply with section 410.3. ST-5 is for residential use only per manufacturer. Table E201.1 is not in 2021 IPC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2362718 |
| Construction | Original | D | 9/23/2026 | BPHILLIPS | BPHILLIPS | LSP - stock area * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2362697 |
| Energy | Original | / | 9/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2362537 |
| Electronic Plan | Original | / | 9/23/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2362481 |
| Enumeration | Original | A | 9/22/2026 | BRENT | BRENT | | | Enumeration | 2362442 |
| Electronic Plan | Original | / | 9/22/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2362439 |
| Submittal 2 | Original | / | 9/22/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2362415 |
| Meridian Ranch Water | Original | D | 7/10/2026 | MERIDIANRANCH | MERIDIANRANCH | | LawrenceGrahem | Meridian Ranch Water | 2333003 |
| Meridian Ranch Waste Water | Original | D | 7/10/2026 | MERIDIANRANCH | MERIDIANRANCH | | LawrenceGrahem | Meridian Ranch Waste Water | 2333002 |
| Plan Coordinator (Main) | Original | D | 9/4/2025 | BRENT | BRENT | Tenant finishes cannot be submitted prior to the issuance of a building permit for the core and shell building. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2206906 |
| Electronic Plan | Original | / | 9/4/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2206897 |
| Waste Water Div | Original | / | 8/26/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2203671 |
| Water Division | Original | / | 8/26/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2203670 |
| Energy | Original | / | 8/26/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2203669 |
| Floodplain | Original | N | 8/26/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 4230319058) | | Floodplain | 2203668 |