| Electronic Plan | Original | / | 12/16/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2248235 |
| Mechanical | Original | D | 12/15/2025 | DALEH | DALEH | This is now an R-2 that requires certain ventilation requirements separate from what an A assembly would require Provide a ventilation schedule and a mechanical schedule showing exhaust fan using No fan in bathroom ? Is kitchen range hood recirculating ? Exhaust to exterior ? Schedule range hood if installing * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2247620 |
| Plumbing | Original | A | 12/15/2025 | SHANEN | SHANEN | | | Plumbing | 2247571 |
| Construction | Original | A | 12/15/2025 | DOUGC | DOUGC | | | Construction | 2247545 |
| Enumeration | Original | A | 12/15/2025 | AMY | AMY | Old utility room will be new unit 2. Unit 6B has been corrected on all of the sheet to Unit 2. North arrow was added to the Architectural sheet along with the new unit numbers being changes to this entire floor. If any of the sheets get changed, out correct the above information. The address change to all of the unit numbers in the building will be completed today. | | Enumeration | 2247249 |
| Electronic Plan | Original | / | 12/15/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2247241 |
| Electronic Plan | Original | / | 12/3/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2243274 |
| Enumeration | Original | A | 12/3/2025 | AMY | AMY | | | Enumeration | 2243136 |
| Electronic Plan | Original | / | 12/2/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2242886 |
| | Original | / | 12/2/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2242852 |
| | Original | / | 12/2/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2242485 |
| Submittal 4 | Original | / | 12/2/2025 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 2242484 |
| Energy | Original | D | 11/26/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2241750 |
| Electrical | Original | D | 11/26/2025 | BERTHA | BERTHA | Pending prior review comments - pending construction review. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2241749 |
| Electronic Plan | Original | / | 11/26/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2241745 |
| Mechanical | Original | D | 11/10/2025 | DALEH | DALEH | Need construction review comments to be addressed Provide mechanical as required * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2234792 |
| Plumbing | Original | D | 11/7/2025 | SHANEN | SHANEN | Construction and enumerations comments must be addressed. Sewage ejector shall comply with section 712. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2234582 |
| Construction | Original | D | 11/7/2025 | DOUGC | DOUGC | Comments not addressed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2234517 |
| Energy | Original | / | 11/7/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2234514 |
| Electronic Plan | Original | / | 11/6/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2234095 |
| Enumeration | Original | D | 11/6/2025 | AMY | AMY | Information that was requested on 8/28/25 and 9/30/25 has not been added to the plan set. Please read prior comments from Enumerations. Contact me if you need more clarification.
The architectural sheet shows unit 106.The electrical & plumbing sheets show Room 6B. Is the work in unit 106 or room 6B? Per Colorado Springs Utilities & USPS has 1505 E Kiowa Street has apt unit 1-5, there is not a unit 106. Provide a floor plan showing all the units on this floor along with the unit numbers. The zip code for this area is 80909 and should be added to the Code Study form. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2233710 |
| Electronic Plan | Original | / | 11/6/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2233698 |
| | Original | / | 11/5/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2233405 |
| | Original | / | 11/5/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2233031 |
| Submittal 3 | Original | / | 11/5/2025 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2233030 |
| Electrical | Original | D | 10/8/2025 | BERTHA | BERTHA | Pending Construction review. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2220861 |
| Electronic Plan | Original | / | 10/8/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2220851 |
| Plumbing | Original | D | 10/7/2025 | SHANEN | SHANEN | Construction and enumerations comments must be addressed. Sewage ejector shall comply with section 712. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2220289 |
| Mechanical | Original | D | 9/30/2025 | DALEH | DALEH | Waiting on construction plan review comments to be addressed Please provide mechanical documents once defined * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2217906 |
| Energy | Original | N | 9/30/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2217814 |
| Construction | Original | D | 9/30/2025 | DOUGC | DOUGC | Original comments not addressed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2217816 |
| Electronic Plan | Original | / | 9/30/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2217801 |
| Enumeration | Original | D | 9/30/2025 | AMY | AMY | The architectural sheet shows unit 106.The electrical & plumbing sheets show Room 6B. Is the work in unit 106 or room 6B? Per Colorado Springs Utilities & USPS has 1505 E Kiowa Street has apt unit 1-5, there is not a unit 106. Provide a floor plan showing all the units on this floor along with the unit numbers. The zip code for this area is 80909 and should be added to the Code Study form. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2217639 |
| Submittal 2 | Original | / | 9/30/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2217413 |
| Electrical | Original | D | 9/16/2025 | BERTHA | BERTHA | Pending Construction and Enumerations review. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2211725 |
| Energy | Original | D | 9/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2211726 |
| Electronic Plan | Original | / | 9/16/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2211688 |
| CO Springs Hazmat | Original | N | 9/8/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2208026 |
| CO Springs Fire | Original | N | 9/8/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Fire | 2208024 |
| Mechanical | Original | D | 9/2/2025 | DALEH | DALEH | Waiting on construction plan review comments to be addressed Please provide mechanical documents once defined * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2205898 |
| Plumbing | Original | D | 9/2/2025 | SHANEN | SHANEN | Construction and enumerations comments must be addressed. Sewage ejector shall comply with section 712. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2205517 |
| CSU Water | Original | N | 9/2/2025 | CSUREVIEW | CSUREVIEW | Backflow okay. No new water service outside of building.MDA | malcuran | CSU Water | 2205501 |
| CSU Waste Water | Original | N | 9/2/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2205500 |
| Construction | Original | D | 8/29/2025 | DOUGC | DOUGC | No record of this unit * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2205436 |
| Electronic Plan | Original | / | 8/29/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2205337 |
| Enumeration | Original | D | 8/28/2025 | AMY | AMY | The architectural sheet shows unit 106.The electrical & plumbing sheets show Room 6B. Is the work in unit 106 or room 6B? Per Colorado Springs Utilities 1505 E Kiowa Street has apt unit 1-5, there is not a unit 106. The zip code for this area is 80909 and should be added to the Code Study form. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2205007 |
| Electronic Plan | Original | / | 8/27/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2204068 |
| Energy | Original | / | 8/27/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2203894 |
| Floodplain | Original | N | 8/27/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6417123003) | | Floodplain | 2203893 |