| EPC Health Dept | Original | D | 10/28/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review application received and not yet approved. Invoice is outstanding. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2229600 |
| Mechanical | Original | A | 10/27/2025 | DALEH | DALEH | | | Mechanical | 2229127 |
| Plumbing | Original | D | 10/27/2025 | SHANEN | SHANEN | Indoor grease trap detail does not comply with section 802.1.1. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2229070 |
| Construction | Original | D | 10/27/2025 | SHELLEY | SHELLEY | Still need framing plans for platforms. Plywood isn't allowed in IIB building unless FRT. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2229036 |
| | Original | / | 10/27/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2228939 |
| | Original | / | 10/27/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2228876 |
| Submittal 3 | Original | / | 10/27/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2228875 |
| CO Springs Fire | Original | A | 10/14/2025 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance.
You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. DFM Plan Review Fee: $296.00 ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2223328 |
| CO Springs Hazmat | Original | N | 10/14/2025 | CSFIRE | CSFIRE | 75 lb CO2 declared | chiptaylor | CO Springs Hazmat | 2223324 |
| Plumbing | Original | D | 10/7/2025 | SHANEN | SHANEN | Provide a grease trap installation detail. Provide a three compartment sink installation detail to show compliance with section 802.1.1. Grease trap GPM does not meet CSU variance letter requirements. Show sizing for each branch of the water distribution system serving multiple fixtures. 3/4"DCW as noted on sheet P1.0 is not sufficiently sized for all branches. Provide a DWV and water distribution isometric drawing and/or riser diagram for the restrooms for clarity. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2220478 |
| EPC Health Dept | Original | D | 10/7/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2220350 |
| Mechanical | Original | D | 10/6/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2219766 |
| Electrical | Original | A | 10/6/2025 | DANIELG | DANIELG | | | Electrical | 2219641 |
| Construction | Original | D | 10/6/2025 | SHELLEY | SHELLEY | See LSP, restrooms, trampoline plans, code study. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2219619 |
| Electronic Plan | Original | / | 10/3/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2219318 |
| Submittal 2 | Original | / | 10/3/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2219098 |
| Electrical | Original | D | 9/19/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2213677 |
| Electronic Plan | Original | / | 9/19/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2213663 |
| CO Springs Fire | Original | D | 9/19/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2213411 |
| CO Springs Hazmat | Original | D | 9/19/2025 | CSFIRE | CSFIRE | Provide CO2 form | chiptaylor | CO Springs Hazmat | 2213410 |
| Plumbing | Original | D | 9/11/2025 | SHANEN | SHANEN | Construction review comments must be addressed. Approved occupant load required to verify compliance with section 403.1. Three compartment sink shown in detail 2 does not comply with section 802.1. Provide required CSU variance letter for the indoor grease interceptor. Show sizing for each branch of the water distribution system serving multiple fixtures. 3/4"DCW as noted on sheet P1.0 is not sufficiently sized for all branches. Provide a DWV and water distribution isometric drawing and/or riser diagram for the restrooms for clarity. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2209750 |
| Mechanical | Original | D | 9/11/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2209603 |
| EPC Health Dept | Original | D | 9/11/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2209591 |
| CSU Water | Original | N | 9/10/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow okay.MDA | malcuran | CSU Water | 2209215 |
| CSU Waste Water | Original | N | 9/10/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building.MDA | malcuran | CSU Waste Water | 2209213 |
| Construction | Original | D | 9/10/2025 | CHRISTINEH | CHRISTINEH | Preliminary review only:
Cannot do a full review on building without all applicable details for entire space * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2209121 |
| Energy | Original | N | 9/10/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2208969 |
| Electronic Plan | Original | / | 9/9/2025 | CHRISTINEH | CHRISTINEH | In Current Review by CHRISTINEH | | Electronic Plan | 2208506 |
| Enumeration | Original | N | 9/4/2025 | BRENT | BRENT | | | Enumeration | 2206922 |
| Electronic Plan | Original | / | 9/4/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2206921 |
| Energy | Original | / | 9/3/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2206123 |
| Floodplain | Original | N | 9/3/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6416404062) | | Floodplain | 2206122 |