| Fountain Zoning | Original | A | 10/31/2025 | ZONINGF | ZONINGF | OK to release for permitting. Use tax 25-066F. KM | KMartinez | Fountain Zoning | 2231436 |
| Fountain Fire | Original | D | 10/20/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Fountain Fire | 2226101 |
| Energy | Original | D | 10/13/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2222736 |
| Electrical | Original | D | 10/13/2025 | BERTHA | BERTHA | Comply with previous review comment - Provide series rated listed breaker combinations.
Remove parallel neutral - no equipment ground in service conductor. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2222735 |
| Electronic Plan | Original | / | 10/13/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2222708 |
| Mechanical | Original | A | 10/9/2025 | TREVORH | TREVORH | Approved; gas only at this time. | | Mechanical | 2221678 |
| Plumbing | Original | D | 10/9/2025 | SHANEN | SHANEN | Water meter and backflow assembly must show compliance with sections 305.4 and 608.15.2.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2221513 |
| Construction | Original | D | 10/9/2025 | BPHILLIPS | BPHILLIPS | Completed IECC form required, along with Comcheck supporting documentation. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2221506 |
| Electronic Plan | Original | / | 10/9/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2221494 |
| Enumeration | Original | A | 10/8/2025 | BRENT | BRENT | | | Enumeration | 2221368 |
| Electronic Plan | Original | / | 10/8/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2221359 |
| Submittal 2 | Original | / | 10/8/2025 | QUINTONW | QUINTONW | Submittal #2 - Phased Commercial C (thru Core and Shell) | | Submittal 2 | 2221302 |
| Fountain Waste Water | Original | A | 10/7/2025 | FNTNSAN | FNTNSAN | | Jmoore3431 | Fountain Waste Water | 2220387 |
| Fountain Zoning | Original | D | 10/6/2025 | ZONINGF | ZONINGF | Plans marked disapproved at Applicant's request to allow for resubmittal of plans. KM | KMartinez | Fountain Zoning | 2220066 |
| Energy | Original | D | 9/25/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2215805 |
| Electrical | Original | D | 9/25/2025 | BERTHA | BERTHA | Currently adopted code is 2023 NEC - revise all references to 2017 NEC.
Provide all conductor size, type and quantity.
Provide series rated listed breaker combinations.
Provide Panel B on the one-line, Provide Panel B schedule.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2215804 |
| Fountain Fire | Original | D | 9/22/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | Fountain Fire | 2214190 |
| Fountain Hazmat | Original | N | 9/22/2025 | CSFIRE | CSFIRE | | chiptaylor | Fountain Hazmat | 2214189 |
| Electronic Plan | Original | / | 9/18/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2212548 |
| Mechanical | Original | D | 9/17/2025 | TREVORH | TREVORH | Disapproved; Need to show location of EWH-1 on plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2212010 |
| Electronic Plan | Original | / | 9/17/2025 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2211987 |
| EPC Health Dept | Original | N | 9/16/2025 | HEALTHDEPT | HEALTHDEPT | Approved for core and shell only.
Retail food establishment plan review will be required with interior finish submittal. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2211706 |
| Plumbing | Original | D | 9/16/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Clarify compliance with section 305.4. Provide gpm and/or square footage served by each component of the roof drainage system. Overflow cutout dimensions are not in compliance with 2021 IPC section 1108.3. All required roof drainage information was not provided on sheet A102. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2211264 |
| Elevators | Original | N | 9/15/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2211239 |
| Construction | Original | D | 9/15/2025 | BPHILLIPS | BPHILLIPS | Site plan, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2210976 |
| Electronic Plan | Original | / | 9/15/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2210838 |
| Enumeration | Original | A | 9/10/2025 | BRENT | BRENT | | | Enumeration | 2209284 |
| Electronic Plan | Original | / | 9/10/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2209266 |
| | Original | / | 9/10/2025 | SYSTEM | SYSTEM | Plan Review fees paid 09/10/2025 for plan submitted 09/10/2025. Submit Date updated to now. Plan now open for review. | | | 2209159 |
| Water Division | Original | / | 9/10/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2209142 |
| Waste Water Div | Original | / | 9/10/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2209143 |
| Energy | Original | / | 9/10/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2209141 |
| Floodplain | Original | N | 9/10/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5530008018) | | Floodplain | 2209140 |