| CO Springs Fire | Original | A | 12/15/2025 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2247242 |
| Electrical | Original | D | 12/9/2025 | BERTHA | BERTHA | Comply with previous review comments. Indicate compliance on the electrical plans for all comments.
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC). . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2245433 |
| Plumbing | Original | N | 12/8/2025 | SHANEN | SHANEN | No plumbing scope indicated. | | Plumbing | 2244986 |
| CO Springs DRE | Original | A | 12/8/2025 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2244894 |
| Electronic Plan | Original | / | 12/5/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2244585 |
| Mechanical | Original | D | 12/5/2025 | TREVORH | TREVORH | Disapproved; Need the Refrigeration calculation for the new split systems * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2244490 |
| Zoning/Planning | Original | / | 12/5/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2244256 |
| Construction | Original | A | 12/5/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2244202 |
| Electronic Plan | Original | / | 12/4/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2244136 |
| Submittal 2 | Original | / | 12/4/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2243944 |
| Plumbing | Original | D | 10/7/2025 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2220586 |
| CO Springs Fire | Original | D | 9/30/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2217732 |
| CO Springs Hazmat | Original | N | 9/30/2025 | CSFIRE | CSFIRE | No Inspection | michael.davis1@color | CO Springs Hazmat | 2217730 |
| Electrical | Original | D | 9/29/2025 | BERTHA | BERTHA | Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2217309 |
| Mechanical | Original | D | 9/29/2025 | TREVORH | TREVORH | Disapproved; Provide The Refrigeration calculations for the added split systems.Need to see construction review comments addressed with regardsto the occupancy load. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2217007 |
| Electronic Plan | Original | / | 9/25/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2215875 |
| CSU Waste Water | Original | N | 9/22/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2214391 |
| CSU Water | Original | N | 9/22/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2214390 |
| CO Springs DRE | Original | A | 9/22/2025 | KDODGE | KDODGE | interior remodel, no change in use. Reconfiguration of level 2 offices/project rooms. | | CO Springs DRE | 2214356 |
| Construction | Original | D | 9/22/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, occupant load calculation * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2214300 |
| Energy | Original | N | 9/22/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2214267 |
| Electronic Plan | Original | / | 9/22/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2214121 |
| Enumeration | Original | N | 9/19/2025 | BRENT | BRENT | | | Enumeration | 2213492 |
| Electronic Plan | Original | / | 9/19/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2213472 |
| | Original | / | 9/18/2025 | SYSTEM | SYSTEM | Plan Review fees paid 09/18/2025 for plan submitted 09/11/2025. Submit Date updated to now. Plan now open for review. | | | 2213186 |
| Floodplain | Original | N | 9/11/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6412402003) | | Floodplain | 2209502 |
| Energy | Original | / | 9/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2209503 |