| Mechanical | Original | D | 5/14/2026 | TREVORH | TREVORH | Disapproved; Need to see Elevator and construction review comments addressed to complete Mechanical Review. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2307327 |
| EPC Health Dept | Original | N | 5/14/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1723 is valid from 4/01/2026- 10/1/2026. To continue any earthmoving operations after 10/1/2026, please reapply for a new permit online through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. MLL | mlockwood | EPC Health Dept | 2307302 |
| Electronic Plan | Original | / | 5/14/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2307084 |
| Plumbing | Original | D | 5/13/2026 | SHANEN | SHANEN | See clouded sections on additional requirements for 2021 IECC block. Remove all references to the mechanical/electrical scope from the plumbing plans. Provide referenced civil drawings to verify water service sizing, water entry location, building drain sizing, building drain location, oil interceptor location, etc. Donala water/waste water dept. approved construction drawings and utility service plan required to verify the plumbing plans correspond with the Donala water/waste water dept. approved plans for water service sizing, water entry location, building drain sizing, building drain location, oil interceptor location, etc. Lavatories must show compliance with 2021 IECC section C404.5.1. Connections between drainage piping and fittings must show compliance with section 706 throughout. Water heater detail must show compliance with 2021 IECC section 404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2306713 |
| Elevators | Original | D | 5/13/2026 | ROBERTV | ROBERTV | Need to provide specifications for Parts Lifts being used to determine any required regulation. Also need to see method of accessible route for second floor mezzanine. See sheets: A1.1 and A1.2. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2306611 |
| Monument Hazmat | Original | A | 5/13/2026 | MONUMENTFIRE | MONUMENTFIRE | Impact fees are due before release of this permit | SBenson9 | Monument Hazmat | 2306513 |
| Monument Fire | Original | A | 5/13/2026 | MONUMENTFIRE | MONUMENTFIRE | Impact fees are due before release of this permit.Your review was done using the 2021 International Fire Code and adopted amendments and policies of Monument Fire District. All permits can be applied for at monumentfire.org/permitsDeferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation.Field Verification Approved plans are subject to field verification. Installations not in accordance with approved plans or applicable codes may require correction.Inspection Scheduling All inspections shall be requested a minimum of 48 hours in advance through Monument Fire. Contact permits@monumentfire.org Approval by Monument Fire does not relieve the applicant from compliance with all other applicable codes, ordinances, and requirements from other agencies having jurisdiction. | SBenson9 | Monument Fire | 2306512 |
| Monument Fire | Original | A | 5/13/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Monument Fire | 2306511 |
| EPC Health Dept | Original | D | 5/12/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2306360 |
| Gas/Elec. Utils | Original | D | 5/12/2026 | CSUREVIEW | CSUREVIEW | Electric - Not in Colorado Springs Utilities' electric service territory.
Gas - Please submit an Application for Gas Service Line Approval, as well as an Application for Elevated Pressure Approval (if needed) to Field Engineering. Forms can be found at https://www.csu.org/Pages/development-files-forms.aspx Contact Jason Luukkonen at 719-668-8331 with coordination questions.
SSH | SHillman | Gas/Elec. Utils | 2306261 |
| CSU Contract Admin. | Original | N | 5/12/2026 | CSUAPPSPRM | CSUAPPSPRM | Gas service territory only. No applicable fees required for this plan set.
AMS | ASweet | CSU Contract Admin. | 2305985 |
| Zoning/Planning | Original | / | 5/11/2026 | DSDLETKE | DSDLETKE | In Current Review by DSDLETKE | | Zoning/Planning | 2305586 |
| Construction | Original | D | 5/11/2026 | SHELLEY | SHELLEY | LSP, accessibility, IECC, Code study form; see plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2305579 |
| Electronic Plan | Original | / | 5/7/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2304503 |
| Enumeration | Original | D | 5/6/2026 | BECKYA | BECKYA | The address is 298 Gleneagle Gate View. Update all plan pages that show the address to include the Code Study Form.
Once the plan has completed reviews, any disapproved plan which will be submitted will need the address updated. If any plans are approved, I can update for you. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2304092 |
| Submittal 2 | Original | / | 5/6/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2304055 |
| Enumeration | Original | D | 3/30/2026 | BECKYA | BECKYA | Upon further review, the tract address is too low for the new dealer ship based on location of access The revised address is 298 Gleneagle Gate View. Please update all plan pages to show new address. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2286610 |
| Plan Coordinator (Main) | Original | D | 9/25/2025 | DANM | DANM | Only one building allowed per submittal. Cross off, remove or grey out from this submittal all drawings and documents related to the car wash building .
Disapprove all remaining departments to allow plan to be resubmitted * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2216067 |
| Enumeration | Original | D | 9/25/2025 | BECKYA | BECKYA | 1. Please remove the plans for the carwash and submit under a separate plan submittal. The address for the carwash is 204 Gleneagle Gate View, we have updated our system to allow for this address to be used for the carwash submittal. 2. The site plan (AS1.0) has been updated to show the addressing for the hail canopies, main dealership building and the carwash. We also added street names. When resubmitting all plans for this development, please add this information to the Site Plan. 3. Enumerations approval is pending the Final recorded Plat for Academy Gateway Subdivision Filing No. 2 . All plans for this project will be disapproved by Enumerations until the recorded Final Plat has been sent to us. Okay to email Becky Allen (beckya@pprbd.org) once the plat has been recorded. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2216066 |
| Electronic Plan | Original | / | 9/25/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2216014 |
| | Original | / | 9/25/2025 | SYSTEM | SYSTEM | Plan Review fees paid 09/25/2025 for plan submitted 09/17/2025. Submit Date updated to now. Plan now open for review. | | | 2215965 |
| Energy | Original | / | 9/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2212160 |
| Waste Water Div | Original | / | 9/17/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2212162 |
| Water Division | Original | / | 9/17/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2212161 |
| Floodplain | Original | N | 9/17/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6206306005) | | Floodplain | 2212159 |