| CSU Water | Original | D | 5/14/2026 | CSUREVIEW | CSUREVIEW | A Utility Service Plan showing the water entry point is required for this project. Contact Utilities Development Services at (719) 668-8259 to discuss requirements. mjg | mgackle | CSU Water | 2307690 |
| Energy | Original | A | 5/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2307484 |
| Plumbing | Original | A | 5/14/2026 | SHANEN | SHANEN | | | Plumbing | 2307483 |
| | Original | / | 5/14/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2307439 |
| | Original | / | 5/14/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2307426 |
| Submittal 5 | Original | / | 5/14/2026 | MELISSAF | MELISSAF | Submittal #5 | | Submittal 5 | 2307425 |
| CO Springs DRE | Original | A | 4/20/2026 | SSADLER | SSADLER | This building plan is for the garage only. Plans approved. No impact fees are due for this permit | | CO Springs DRE | 2295296 |
| CO Springs DRE | Original | D | 4/20/2026 | SSADLER | SSADLER | Site dimensional standards met. However, the only remaining comment is to collect park, school, police and fire fees. Plans are approved and once fees are collected, the building permit can be approved. Please contact DRE at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2295200 |
| City Engr | Original | A | 4/17/2026 | HVO | HVO | EDRD has no comments. | | City Engr | 2294505 |
| CSU Water | Original | D | 4/16/2026 | CSUREVIEW | CSUREVIEW | An approved Utility Service Plan (USP) for Project 2024-C1001 that shows the scope indicated on this permit set must be uploaded. No existing approved USP for the continuation of the scope shown on sheet P1.1 was found. Call UDS at 719-668-8259 with questions. SSH | SHillman | CSU Water | 2294308 |
| CSU Waste Water | Original | N | 4/16/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2294299 |
| Gas/Elec. Utils | Original | A | 4/16/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2294297 |
| Energy | Original | D | 4/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2294282 |
| Electrical | Original | A | 4/16/2026 | DANIELG | DANIELG | | | Electrical | 2294281 |
| Plumbing | Original | D | 4/16/2026 | SHANEN | SHANEN | Reviewer could not verify point of connection and continuation of 3/4"CW with referenced civil drawings. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2294231 |
| Zoning/Planning | Original | / | 4/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2294188 |
| Mechanical | Original | A | 4/16/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2294177 |
| Construction | Original | A | 4/16/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2294168 |
| Electronic Plan | Original | / | 4/16/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2294114 |
| Submittal 4 | Original | / | 4/16/2026 | JAY | JAY | Submittal #4 | | Submittal 4 | 2294048 |
| CO Springs DRE | Original | D | 4/9/2026 | SSADLER | SSADLER | Previous comments not addressed. Upload the final approved development plan and the final approved landscaping and irrigation plans. | | CO Springs DRE | 2291156 |
| City Engr | Original | D | 4/8/2026 | JDAGNILLO | JDAGNILLO | Please address previous comment - Include a copy of the approved Development Plan and a copy of the Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2290635 |
| Zoning/Planning | Original | / | 4/8/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2290261 |
| Energy | Original | D | 4/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2289696 |
| Mechanical | Original | A | 4/7/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2289695 |
| CSU Water | Original | D | 4/6/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set for the specific application. Plumbing plans do not match the Approved Construction Plans. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2289433 |
| CSU Waste Water | Original | D | 4/6/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set for the specific application. Plumbing plans do not match the Approved Construction Plans. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2289431 |
| Gas/Elec. Utils | Original | D | 4/6/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2289429 |
| Plumbing | Original | D | 4/6/2026 | SHANEN | SHANEN | 3/4"CW point of connection is not shown on referenced civil drawings. Plumbing plans must correspond with the CSU approved USP. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2289376 |
| Electrical | Original | D | 4/6/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2289272 |
| Construction | Original | D | 4/6/2026 | BPHILLIPS | BPHILLIPS | Provide supporting documentation for Comcheck compliance. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2289258 |
| Enumeration | Original | A | 4/3/2026 | BECKYA | BECKYA | | | Enumeration | 2288456 |
| | Original | / | 4/2/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2288317 |
| | Original | / | 4/2/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2288297 |
| Submittal 3 | Original | / | 4/2/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2288296 |
| EPC Health Dept | Original | N | 2/11/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1665 is valid from 10/01/2025-04/01/2026. To continue any earthmoving operations after 04/01/2026, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2265738 |
| CO Springs Fire | Original | N | 2/9/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Fire | 2264540 |
| CO Springs DRE | Original | D | 2/4/2026 | SSADLER | SSADLER | Previous denial comments not addressed. Upload the final approved and stamped development plan, final landscaping and irrigation plans.
Final recorded plat on file. Assurances are posted. | | CO Springs DRE | 2263241 |
| Energy | Original | D | 2/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2263056 |
| Mechanical | Original | D | 2/3/2026 | TREVORH | TREVORH | Disapproved; Need to see construction review comments addressed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2263055 |
| CSU Waste Water | Original | D | 2/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Waste Water | 2262922 |
| CSU Water | Original | D | 2/3/2026 | CSUREVIEW | CSUREVIEW | Plumbing plan does not match the approved USP. Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Water | 2262921 |
| Gas/Elec. Utils | Original | D | 2/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | Gas/Elec. Utils | 2262918 |
| Zoning/Planning | Original | / | 2/3/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2262883 |
| Electrical | Original | D | 2/3/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2262872 |
| City Engr | Original | D | 2/3/2026 | HVO | HVO | Please see previous comment- include a copy of the approved Development Plan | | City Engr | 2262858 |
| Plumbing | Original | D | 2/3/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All condensate piping related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. 3/4"CW serving HB-1 is not shown on referenced civil drawings. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2262826 |
| Construction | Original | D | 2/3/2026 | BPHILLIPS | BPHILLIPS | Comcheck not compliant * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2262787 |
| Enumeration | Original | A | 2/2/2026 | BECKYA | BECKYA | | | Enumeration | 2262371 |
| Submittal 2 | Original | / | 2/2/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2262284 |
| CSU Contract Admin. | Original | A | 1/26/2026 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved & all applicable Development fees/charges paid. BS | bschifferstein | CSU Contract Admin. | 2259839 |
| Energy | Original | D | 10/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2220944 |
| Plumbing | Original | D | 10/8/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All condensate piping related items shall be on the mechanical plans.Remove all references to condensate piping from the plumbing plans. CSU comments must be addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2220943 |
| CO Springs Hazmat | Original | N | 9/30/2025 | CSFIRE | CSFIRE | No Inspection | michael.davis1@color | CO Springs Hazmat | 2217414 |
| CO Springs Fire | Original | D | 9/30/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | CO Springs Fire | 2217412 |
| Electrical | Original | D | 9/29/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2217344 |
| Electronic Plan | Original | / | 9/29/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2217339 |
| CO Springs DRE | Original | D | 9/29/2025 | SSADLER | SSADLER | Upload the final approved development plan. | | CO Springs DRE | 2217294 |
| CSU Water | Original | D | 9/24/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Add the two details to the plumbing plan set. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2215597 |
| CSU Waste Water | Original | D | 9/24/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2215595 |
| Gas/Elec. Utils | Original | D | 9/24/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2215594 |
| EPC Health Dept | Original | D | 9/24/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2215257 |
| Mechanical | Original | D | 9/24/2025 | TREVORH | TREVORH | Disapproved; Need to see construction and Enumeration Review comments addressed,show condensate routing and point of disposal on Mechanical plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2215137 |
| City Engr | Original | D | 9/23/2025 | HVO | HVO | Please include a copy of Development Plan, a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan, and a copy of the approved Stormwater Enterprise approved Permanent Control Measures in the electronic building permit set | | City Engr | 2214861 |
| CSU Contract Admin. | Original | D | 9/23/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2214828 |
| Zoning/Planning | Original | / | 9/23/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2214770 |
| Construction | Original | D | 9/23/2025 | BPHILLIPS | BPHILLIPS | Occupant load, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2214676 |
| Electronic Plan | Original | / | 9/22/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2214366 |
| Enumeration | Original | D | 9/17/2025 | BECKYA | BECKYA | 1. The address for this garage is 5964 Bell Rock Point. Update the Code Study Form to show the correct address. 2. Update the site plan on page A0.3 to show all street names and addressing for this development. Highlight area of work. 3. When submitting future plans for this development, submit under the assigned address(es) not the address of the existing home. 4. Enumerations approval will be pending for all plans for this development until the Final Plat for Village at Cottonwood Creek has been recorded and plat fees paid. Once it is recorded, okay to send to me Becky Allen (beckya@pprbd.org) and then I can approve the plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2212339 |
| Electronic Plan | Original | / | 9/17/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2212215 |
| | Original | / | 9/17/2025 | SYSTEM | SYSTEM | Plan Review fees paid 09/17/2025 for plan submitted 09/17/2025. Submit Date updated to now. Plan now open for review. | | | 2212178 |
| Energy | Original | / | 9/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2212167 |
| Floodplain | Original | N | 9/17/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5306306008) | | Floodplain | 2212166 |