| Stormwater | Original | A | 2/24/2026 | JLANDON | JLANDON | | | Stormwater | 2270445 |
| City Engr | Original | A | 2/23/2026 | HVO | HVO | EDRD has no additional comments. | | City Engr | 2269752 |
| | Original | / | 2/20/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2269295 |
| | Original | / | 2/19/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2268380 |
| Submittal 5 | Original | / | 2/19/2026 | MELISSAF | MELISSAF | Submittal #5 | | Submittal 5 | 2268379 |
| Stormwater | Original | D | 2/17/2026 | JLANDON | JLANDON | Upload full approved final phase Grading and Erosion Control Plan showing retaining wall locations and top of wall/bottom of wall elevations. Locations and elevations should match between DP and GEC Plan. | | Stormwater | 2267261 |
| CO Springs DRE | Original | A | 2/12/2026 | SSADLER | SSADLER | Plans are consistent with the approved development plans. | | CO Springs DRE | 2266091 |
| City Engr | Original | D | 2/12/2026 | JDAGNILLO | JDAGNILLO | Geological hazard report has been approved by the City (Project Dox #STM-REV24-0252).
Please include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2265968 |
| Zoning/Planning | Original | / | 2/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2265864 |
| CSU Water | Original | A | 2/11/2026 | CSUREVIEW | CSUREVIEW | Approved development plan and utility construction drawings provided with permit set. PSD | PDosch | CSU Water | 2265382 |
| CSU Waste Water | Original | A | 2/11/2026 | CSUREVIEW | CSUREVIEW | Approved development plan and utility construction drawings provided with permit set. PSD | PDosch | CSU Waste Water | 2265378 |
| Gas/Elec. Utils | Original | A | 2/11/2026 | CSUREVIEW | CSUREVIEW | Comments addressed. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | Gas/Elec. Utils | 2265372 |
| Electrical | Original | A | 2/10/2026 | DANIELG | DANIELG | | | Electrical | 2265321 |
| Construction | Original | A | 2/10/2026 | DOUGC | DOUGC | | | Construction | 2265311 |
| Mechanical | Original | N | 2/10/2026 | TCRIPPEN | TCRIPPEN | No mechanical on pool plan | | Mechanical | 2265248 |
| Enumeration | Original | A | 2/10/2026 | BECKYA | BECKYA | | | Enumeration | 2265209 |
| | Original | / | 2/10/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2265203 |
| | Original | / | 2/10/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2265150 |
| Submittal 4 | Original | / | 2/10/2026 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 2265149 |
| Mechanical | Original | D | 2/4/2026 | TCRIPPEN | TCRIPPEN | Disapproved this plan should be pool only ? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2263338 |
| CSU Contract Admin. | Original | N | 2/4/2026 | CSUAPPSPRM | CSUAPPSPRM | No additional fees required. Pool was included in original plan set and approved.
AMS | ASweet | CSU Contract Admin. | 2263278 |
| CO Springs DRE | Original | D | 2/3/2026 | SSADLER | SSADLER | Previous comments not addressed. Upload the approved and stamped development plans.
These plans have reached the maximum allotted plan reviews, and a re-review fee has been assessed. Fees must be paid prior to further reviews. To pay fees for permit review please follow the link provided. https://aca-prod.accela.com/COSPRINGS/Default.aspx
Click on “Building” tab and enter record number BLDREV-26-00098 or enter required information in fields provided. | | CO Springs DRE | 2262989 |
| City Engr | Original | D | 2/3/2026 | HVO | HVO | Please see previous comment. | | City Engr | 2262859 |
| Electrical | Original | A | 2/3/2026 | DANIELG | DANIELG | | | Electrical | 2262802 |
| CSU Water | Original | D | 2/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Water | 2262756 |
| CSU Waste Water | Original | D | 2/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Waste Water | 2262755 |
| Gas/Elec. Utils | Original | D | 2/3/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | Gas/Elec. Utils | 2262753 |
| CSU Contract Admin. | Original | D | 2/3/2026 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted: Requires approved Commercial Water Meter Sizing Form (CWMSF) as long as existing meter is sufficient no additional fees are required. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. BS | bschifferstein | CSU Contract Admin. | 2262748 |
| Electrical | Original | D | 2/3/2026 | DANIELG | DANIELG | Pending pool splice to clubhouse plans. Must update pool equipment room and panel schedule. P# C187141
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2262661 |
| Zoning/Planning | Original | / | 2/3/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2262657 |
| Plumbing | Original | N | 2/3/2026 | SHANEN | SHANEN | Pool deck drains must comply with section 802.1.4 Swimming pools. Where waste water from swimming pools, backwash from filters, and water from pool deck drains discharge to the building drainage system (as in this jurisdiction), the discharge shall be through an indirect waste pipe by means of an air gap. Discharging pool deck drains to the storm sewer is prohibited in this jurisdiction. PROCEED AT YOUR OWN RISK. | | Plumbing | 2262656 |
| Construction | Original | D | 2/3/2026 | DOUGC | DOUGC | CSF // LSP * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2262651 |
| Enumeration | Original | A | 2/2/2026 | BECKYA | BECKYA | | | Enumeration | 2262105 |
| | Original | / | 2/2/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2261970 |
| | Original | / | 1/30/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2261736 |
| Submittal 3 | Original | / | 1/30/2026 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2261735 |
| CO Springs Fire | Original | N | 12/16/2025 | CSFIRE | CSFIRE | Life safety inspection of pool deck area will be performed as part of the main building fire inspection. | chiptaylor | CO Springs Fire | 2247981 |
| CO Springs Hazmat | Original | N | 12/16/2025 | CSFIRE | CSFIRE | Pool chemicals under permit quantities per hazmat forms provided with main building. | chiptaylor | CO Springs Hazmat | 2247977 |
| CO Springs DRE | Original | D | 12/15/2025 | SSADLER | SSADLER | Previous comments not addressed. Upload the approved and stamped development plans. | | CO Springs DRE | 2247550 |
| CSU Contract Admin. | Original | D | 12/11/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) as long as existing meter is sufficient no additional fees are required.
AMS | ASweet | CSU Contract Admin. | 2246790 |
| Mechanical | Original | D | 12/11/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Provide new page with current stamp and date remove all clouds except for the new splice * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2246621 |
| City Engr | Original | D | 12/11/2025 | HVO | HVO | The geo-hazard report has not been approved by the City engineer. Please upload a copy of the approved Development Plan, the Stormwater Enterprise approved Grading & Erosion Control Plan, and a copy of the approved Stormwater Enterprise approved Permanent Control Measures in the electronic building permit set | | City Engr | 2246614 |
| Gas/Elec. Utils | Original | D | 12/11/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | Gas/Elec. Utils | 2246559 |
| CSU Water | Original | D | 12/11/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Water | 2246558 |
| CSU Waste Water | Original | D | 12/11/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Waste Water | 2246557 |
| Electrical | Original | D | 12/11/2025 | DANIELG | DANIELG | Pending pool splice to clubhouse plans. Must update pool equipment room and panel schedule. P# C187141
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2246528 |
| Zoning/Planning | Original | / | 12/11/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2246332 |
| Plumbing | Original | N | 12/11/2025 | SHANEN | SHANEN | | | Plumbing | 2246281 |
| Electronic Plan | Original | / | 12/11/2025 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2246280 |
| Construction | Original | D | 12/10/2025 | DOUGC | DOUGC | Life Safety Plan // Structural Plans // Missing Architectural sheets * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2246247 |
| Enumeration | Original | A | 12/10/2025 | BECKYA | BECKYA | | | Enumeration | 2246066 |
| Submittal 2 | Original | / | 12/10/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2246034 |
| CO Springs Fire | Original | D | 10/20/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2226197 |
| CO Springs Hazmat | Original | D | 10/20/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2226194 |
| CO Springs DRE | Original | D | 10/14/2025 | SSADLER | SSADLER | Upload the approved stamped development plan | | CO Springs DRE | 2223663 |
| Mechanical | Original | D | 10/13/2025 | TCRIPPEN | TCRIPPEN | Disapproved missing gas lines ? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2222963 |
| CSU Contract Admin. | Original | D | 10/13/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) as long as existing meter is sufficient no additional fees are required.
AMS | ASweet | CSU Contract Admin. | 2222820 |
| Electrical | Original | D | 10/10/2025 | DANIELG | DANIELG | Pending pool splice to clubhouse plans. Must update pool equipment room and panel schedule.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2222462 |
| EPC Health Dept | Original | N | 10/10/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. KB. | KBauer | EPC Health Dept | 2222361 |
| City Engr | Original | D | 10/9/2025 | HVO | HVO | EDRD has determined geological hazards exist in this area and will require a Geologic Hazard Report to be required for this site. Please submit it to EDRD through our electronic review system called ProjectDox. Below is a link to ProjectDox and a user manual.
https://coloradosprings.gov/stormwater/planreview
Once the report has been approved please upload the signed report with this building submission set. | | City Engr | 2221762 |
| Plumbing | Original | N | 10/9/2025 | SHANEN | SHANEN | | | Plumbing | 2221707 |
| Zoning/Planning | Original | / | 10/9/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2221690 |
| CSU Water | Original | D | 10/9/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2221582 |
| CSU Waste Water | Original | D | 10/9/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2221581 |
| Gas/Elec. Utils | Original | D | 10/9/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2221580 |
| Construction | Original | D | 10/9/2025 | DOUGC | DOUGC | Life Safety Plan // Soils * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2221553 |
| Electronic Plan | Original | / | 10/8/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2221405 |
| Enumeration | Original | A | 10/8/2025 | BECKYA | BECKYA | Address to the apartment should have been used on the plans 3155 Athos Hts. Enumerations updated the address on all pages, if the plans are resubmitted, please be sure to update to the correct address. | | Enumeration | 2221248 |
| | Original | / | 10/8/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/08/2025 for plan submitted 09/18/2025. Submit Date updated to now. Plan now open for review. | | | 2221153 |
| Energy | Original | N | 9/18/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2213139 |
| Floodplain | Original | N | 9/18/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7336200026) | | Floodplain | 2213137 |