| EPC Health Dept | Original | N | 11/7/2025 | HEALTHDEPT | HEALTHDEPT | Colorado Department of Health and Environment Air Pollutant Emission Notice (APEN) obtained. MLL | mlockwood | EPC Health Dept | 2234295 |
| Ellicott Hazmat | Original | D | 10/27/2025 | ELLICOTTFIRE | ELLICOTTFIRE | Are you going to have any CO2 or nitrogen and how much alcohol will be stored. | ELLICOTTFD | Ellicott Hazmat | 2229398 |
| Ellicott Fire | Original | D | 10/27/2025 | ELLICOTTFIRE | ELLICOTTFIRE | Type II-B 10,000 square feet S-1 Occupancy NON-SPRINKLERED 35’ tall
Table B105.1(2) 2,250 gpm for 2 hours
Table C102.1 2 hydrants, 450 average spacing, 225 hose lay
D103.1 – Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet, exclusive of shoulders.
D104.1Buildings exceeding three stories or 30’ in height. Buildings or facilities exceeding 30 feet or three stories in height shall have at least two means of fire apparatus access for each structure
B103.1 shall not apply due to the hazardous contents of the structure.
A utility service plan for the fire hydrants, associated pumps and the cistern/tank is required. The plans will not be approved until these requirements are met and seen.
Further infrastructure will need to be provided up into including Fire Station, Road improvement / requirements, fire protection water. | ELLICOTTFD | Ellicott Fire | 2229397 |
| Ellicott Fire | Original | D | 10/27/2025 | ELLICOTTFIRE | ELLICOTTFIRE | Are you going to have any CO2 or Nitrogen, and how much alcohol is being stored. | ELLICOTTFD | Ellicott Fire | 2229394 |
| EPC Health Dept | Original | D | 10/19/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2225807 |
| Energy | Original | D | 10/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2224996 |
| Electrical | Original | D | 10/16/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2224995 |
| Electronic Plan | Original | / | 10/16/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2224985 |
| Mechanical | Original | A | 10/16/2025 | DALEH | DALEH | | | Mechanical | 2224840 |
| Plumbing | Original | D | 10/15/2025 | SHANEN | SHANEN | S occupancy with an occupant load of 20 requires compliance with section 403.1. Service sink and drinking fountain required. Show water service extending a minimum of 30" beyond the exterior walls. Water service sizing and water entry location must correspond with the USP. Not in CSU jurisdiction and water meter assembly must comply with County Water requirements. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2224395 |
| Elevators | Original | N | 10/15/2025 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2224167 |
| County Zoning | Original | D | 10/14/2025 | DSDDEAN2 | DSDDEAN2 | Planning and Community Development Fil No PPR2517 is still in review. Staff sent a resubmittal request to the applicant on 8/20/2025 and are currently awaiting resubmittal from the applicant so we may re-review the documents that were requested to be revised. Please resbumit documents with comments addressed so we may review and move forward to approval of the plans. | | County Zoning | 2224058 |
| CSU Contract Admin. | Original | N | 10/14/2025 | CSUAPPSPRM | CSUAPPSPRM | Gas service territory only. No applicable fees required for this plan set from CSU. Please contact area service provider for applicable fees.
AMS | ASweet | CSU Contract Admin. | 2224029 |
| Gas/Elec. Utils | Original | D | 10/14/2025 | CSUREVIEW | CSUREVIEW | County Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2223899 |
| Zoning/Planning | Original | / | 10/14/2025 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2223765 |
| Construction | Original | D | 10/14/2025 | BPHILLIPS | BPHILLIPS | Metal building plans must be stamped by a Colorado-licensed design professional. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2223528 |
| Energy | Original | / | 10/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2223432 |
| Electronic Plan | Original | / | 10/14/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2223391 |
| Enumeration | Original | D | 10/13/2025 | BRENT | BRENT | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2223284 |
| Electronic Plan | Original | / | 10/13/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2223283 |
| | Original | / | 10/9/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/09/2025 for plan submitted 10/09/2025. Submit Date updated to now. Plan now open for review. | | | 2222249 |
| Waste Water Div | Original | / | 10/9/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2222196 |
| Water Division | Original | / | 10/9/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2222195 |
| Energy | Original | / | 10/9/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2222194 |
| Floodplain | Original | N | 10/9/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 3414108001) | | Floodplain | 2222193 |