| CO Springs Fire | Original | A | 11/19/2025 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2238688 |
| CO Springs DRE | Original | A | 11/17/2025 | SSADLER | SSADLER | Approved for an interior remodel. The only changes to the parking are the addition of ADA signage and re striping. | | CO Springs DRE | 2237432 |
| Energy | Original | D | 11/13/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2236366 |
| Mechanical | Original | A | 11/13/2025 | TREVORH | TREVORH | Approved; | | Mechanical | 2236365 |
| Plumbing | Original | A | 11/13/2025 | SHANEN | SHANEN | | | Plumbing | 2236342 |
| Electrical | Original | D | 11/13/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2236252 |
| Zoning/Planning | Original | / | 11/13/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2236229 |
| Construction | Original | A | 11/13/2025 | BRIANB | BRIANB | | | Construction | 2236221 |
| Electronic Plan | Original | / | 11/13/2025 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2236213 |
| Enumeration | Original | N | 11/12/2025 | AMY | AMY | | | Enumeration | 2235825 |
| Electronic Plan | Original | / | 11/12/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2235807 |
| Submittal 2 | Original | / | 11/12/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2235798 |
| CO Springs Hazmat | Original | N | 10/30/2025 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2230873 |
| CO Springs Fire | Original | D | 10/30/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2230817 |
| CO Springs DRE | Original | D | 10/27/2025 | SSADLER | SSADLER | Label the specific type of work that will be done to the parking lot. If no changes are to be made, show this on the construction sheets. | | CO Springs DRE | 2229043 |
| Zoning/Planning | Original | / | 10/24/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2228745 |
| Energy | Original | D | 10/24/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2228445 |
| Electrical | Original | D | 10/24/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2228444 |
| Electronic Plan | Original | / | 10/24/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2228431 |
| Mechanical | Original | A | 10/23/2025 | TREVORH | TREVORH | Approved; | | Mechanical | 2228183 |
| Plumbing | Original | D | 10/23/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping and condensate piping related items shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. Connections between drainage piping and fittings do not comply with section 706 as drawn. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2228090 |
| CSU Water | Original | N | 10/23/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 2228079 |
| CSU Waste Water | Original | N | 10/23/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 2228078 |
| Enumeration | Original | N | 10/23/2025 | AMY | AMY | | | Enumeration | 2228060 |
| Construction | Original | A | 10/23/2025 | BRIANB | BRIANB | | | Construction | 2228019 |
| Energy | Original | N | 10/23/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2228015 |
| Electronic Plan | Original | / | 10/23/2025 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2227858 |
| Enumeration | Original | N | 10/22/2025 | AMY | AMY | Address to the building was added for you on pages A0.0A & A0.2A. If these sheets get changed out address the addressing. | | Enumeration | 2227761 |
| Electronic Plan | Original | / | 10/22/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2227744 |
| | Original | / | 10/22/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/22/2025 for plan submitted 10/21/2025. Submit Date updated to now. Plan now open for review. | | | 2227722 |
| Energy | Original | / | 10/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2226486 |
| Floodplain | Original | N | 10/21/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6305404018) | | Floodplain | 2226484 |