| CO Springs Fire | Original | D | 11/5/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2233363 |
| CO Springs Hazmat | Original | D | 11/5/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2233362 |
| Electrical | Original | D | 11/4/2025 | BERTHA | BERTHA | Information must be supplied and verified at time of plan submittal. Clarify if Panel is new / existing or relocated.
Comply with C405.11 - 2021 IECC
Provide available fault current and withstand rating for new air conditioning / refrigeration equipment. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2232890 |
| CO Springs DRE | Original | D | 11/4/2025 | CVANAPPLEDORN | CVANAPPLEDORN | It appears that this is a change of use within the building. Warehouse use is a permitted use, but you will then need to update the code study to reflect that change from the existing use to the new warehouse use. This section has been circled on the code study. | | CO Springs DRE | 2232707 |
| Electronic Plan | Original | / | 11/4/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2232435 |
| Zoning/Planning | Original | / | 10/31/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2231429 |
| Mechanical | Original | D | 10/30/2025 | DALEH | DALEH | Waiting on construction review comments to be addressed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2231048 |
| CSU Water | Original | N | 10/30/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2230863 |
| CSU Waste Water | Original | N | 10/30/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2230860 |
| Plumbing | Original | D | 10/30/2025 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1.Show piping to point of connection and sizing at the point of connection. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2230845 |
| Energy | Original | N | 10/30/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2230715 |
| Construction | Original | D | 10/30/2025 | DOUGC | DOUGC | Code Study Form // Missing Structural Plans // Life Safety Plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2230712 |
| Electronic Plan | Original | / | 10/29/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2230350 |
| Enumeration | Original | N | 10/22/2025 | BECKYA | BECKYA | | | Enumeration | 2227775 |
| Electronic Plan | Original | / | 10/22/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2227749 |
| | Original | / | 10/22/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/22/2025 for plan submitted 10/22/2025. Submit Date updated to now. Plan now open for review. | | | 2227493 |
| Energy | Original | / | 10/22/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2227480 |
| Floodplain | Original | N | 10/22/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6319201003) | | Floodplain | 2227478 |