| Electronic Plan | Original | / | 2/2/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2262370 |
| EPC Health Dept | Original | A | 2/2/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. KB. | KBauer | EPC Health Dept | 2262291 |
| CO Springs Hazmat | Original | A | 1/28/2026 | CSFIRE | CSFIRE | Deferred Submital CO2 for Beverage Dispensing. Please have your CO2 contractor submit the hazmat permit for CO2 through the Accela ACA. No TCO or CO will be issued until this permit is approved. | mark.stanwood@colora | CO Springs Hazmat | 2260759 |
| CO Springs Hazmat | Original | D | 1/27/2026 | CSFIRE | CSFIRE | HAZMAT - Defered for CO2 Deferred Submittal for CO2 for Beverage Dispensing. Please have your CO2 contractor submit for a Compressed gas permit directly through the Acella ACA portal. No CO or TCO will be give unit the permit is approved | mark.stanwood@colora | CO Springs Hazmat | 2260618 |
| CO Springs Fire | Original | A | 1/21/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2258152 |
| CO Springs DRE | Original | D | 1/16/2026 | SSADLER | SSADLER | Previous comments not addressed.
Upload the approval letter, the approved and stamped development plan, final recorded plat, final approved landscaping and irrigation plans. All assurances for private improvements must be posted. Citywide Impact fees must be paid prior to building permit issuance. | | CO Springs DRE | 2257333 |
| EPC Health Dept | Original | D | 1/15/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | EPC Health Dept | 2256688 |
| CSU Contract Admin. | Original | D | 1/15/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. JMD | jdemello | CSU Contract Admin. | 2256614 |
| Mechanical | Original | D | 1/14/2026 | TREVORH | TREVORH | Disapproved; Still Need to see the Refrigeration calculations for the walk in cooler to verify if leakage alarm will be required . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2256474 |
| City Engr | Original | D | 1/14/2026 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (Project Dox #STM-REV25-1007) | | City Engr | 2256451 |
| Electronic Plan | Original | / | 1/14/2026 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2256435 |
| Zoning/Planning | Original | / | 1/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2256335 |
| CSU Water | Original | D | 1/14/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Requires approved development plan and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Water | 2256328 |
| CSU Waste Water | Original | D | 1/14/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Requires approved development plan and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Waste Water | 2256327 |
| Gas/Elec. Utils | Original | D | 1/14/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Requires approved development plan and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | Gas/Elec. Utils | 2256326 |
| Construction | Original | A | 1/14/2026 | BRIANB | BRIANB | | | Construction | 2256275 |
| Plumbing | Original | D | 1/14/2026 | SHANEN | SHANEN | All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. Water service and water entry location does not comply with CSU (Colorado Springs Utilities) water line extension and service standards. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, grease interceptor location, etc. Two way cleanout location does not comply with CO state amendment to section 708.1.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2256089 |
| Electronic Plan | Original | / | 1/14/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2256071 |
| Enumeration | Original | A | 1/13/2026 | AMY | AMY | | | Enumeration | 2255913 |
| Electronic Plan | Original | / | 1/13/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2255909 |
| Submittal 2 | Original | / | 1/13/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2255802 |
| Electrical | Original | D | 11/19/2025 | BERTHA | BERTHA | Comply with 250.122 NEC
Provide all conductor size, type and quantity.
Provide series rated listed combinations
Provide legible power plans.
Provide electrical plans with room names on them.
Provide fault current information (SCCR, AIC, SCA)in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment
Comply with Colorado Springs Utilities Electric Line Extension Service Standards - CT's
Provide Panel BDP on one-line and floor plan.
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2238660 |
| Energy | Original | D | 11/19/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2238661 |
| Electronic Plan | Original | / | 11/11/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2235372 |
| CO Springs Fire | Original | D | 11/10/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2235071 |
| City Engr | Original | D | 11/6/2025 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (Project Dox #STM-REV25-1009) | | City Engr | 2233795 |
| CO Springs DRE | Original | D | 11/6/2025 | SSADLER | SSADLER | Upload the approval letter, the approved and stamped development plan, final recorded plat, final approved landscaping and irrigation plans. All assurances for private improvements must be posted. Citywide Impact fees must be paid prior to building permit issuance. | | CO Springs DRE | 2233709 |
| Mechanical | Original | D | 11/6/2025 | TREVORH | TREVORH | Disapproved; All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. Need the Refrigeration calculations for the walk in cooler. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2233520 |
| Electronic Plan | Original | / | 11/5/2025 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2233401 |
| Plumbing | Original | D | 11/5/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping and condensate piping related items shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Heated water supply piping shall comply with 2021 IECC section C404. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, grease interceptor location, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Three compartment sink detail does not comply with section 802.1.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2233141 |
| Elevators | Original | N | 11/4/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2232918 |
| EPC Health Dept | Original | D | 11/3/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2232319 |
| Zoning/Planning | Original | / | 11/3/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2232084 |
| Gas/Elec. Utils | Original | D | 11/3/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 2232079 |
| CSU Water | Original | D | 11/3/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Water | 2232077 |
| CSU Waste Water | Original | D | 11/3/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2232075 |
| Construction | Original | D | 11/3/2025 | BRIANB | BRIANB | see sheet G001 - LSP * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2232069 |
| Electronic Plan | Original | / | 10/31/2025 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2231859 |
| Enumeration | Original | A | 10/30/2025 | AMY | AMY | | | Enumeration | 2230998 |
| Electronic Plan | Original | / | 10/30/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2230986 |
| | Original | / | 10/30/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/30/2025 for plan submitted 10/29/2025. Submit Date updated to now. Plan now open for review. | | | 2230874 |
| CSU Contract Admin. | Original | D | 10/30/2025 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) approved. However requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate.
BS | bschifferstein | CSU Contract Admin. | 2230781 |
| Energy | Original | / | 10/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2230283 |
| Floodplain | Original | N | 10/29/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6434111011) | | Floodplain | 2230281 |