| Energy | Original | D | 11/26/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2241715 |
| Mechanical | Original | D | 11/26/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2241714 |
| Electrical | Original | D | 11/25/2025 | BERTHA | BERTHA | Pending approval in Enumerations - see Enumeration review comments. Multi-meter services must include a list of enumerated addresses on the one-line diagram.
Pending approval in Elevators - see Elevator review comments.
Provide elevator horsepower on the one-line
Comply with 230.95 NEC
Differentiate equipment designation - RNW
Provide compliance with 250.66 on the one-line diagram
Add the following note on the one-line sheet “Documentation confirming compliance with 620.62 is required prior to final.”
Provide overall floorplans - clearly indicate the location of all electric service gear - panels, transformers, disconnects, etc.
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment
Show required EPO location (680.41 NEC).
Note required encapsulation inspection (680.23(B)(2)(b) NEC ).
Note compliance with 680.26 NEC.
Indicate compliance with 680.14
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior), and C405.2.8 (Parking Garages), where applicable.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Complete re-review necessary. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2241216 |
| Electronic Plan | Original | / | 11/24/2025 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2240625 |
| Stormwater | Original | D | 11/21/2025 | JLANDON | JLANDON | Upload full approved Development Plan and final phase Grading and Erosion Control Plan showing retaining wall locations and top of wall/bottom of wall elevations. Locations and elevations should match between DP and GEC Plan. | | Stormwater | 2240033 |
| Plumbing | Original | D | 11/20/2025 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2239575 |
| EPC Health Dept | Original | D | 11/20/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2239113 |
| Electronic Plan | Original | / | 11/19/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2238976 |
| Elevators | Original | D | 11/19/2025 | ROBERTV | ROBERTV | Need site specific shop drawings and power data for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
See sheets: A123, A611-616, E002, E108.A, E108.B, E108.C, E108.D, E114.B, E119.B, E119.C, E119.D, M104.2, M109.1, M109.2, M109.3, M109.4. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2238966 |
| City Engr | Original | D | 11/19/2025 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set.
Please submit financial assurances for all public street improvements along Sierra Madre St. must be posted prior to building permit issuance by City Engineering. In addition, public street construction plans must be submitted separately to Engineering Development Review and Traffic Engineering and reviewed/approved prior to beginning of construction of all public right-of-way improvements. Thank you. | | City Engr | 2238550 |
| CO Springs DRE | Original | D | 11/19/2025 | SSADLER | SSADLER | Upload the final approved development plan that is stamped by the Land Use Review. Upload the approval letter. Upload the final recorded plat. Upload the final approved and stamped landscaping and irrigation plans. Private assurances must be posted. Citywide Impact fees must be paid prior to building permit release. | | CO Springs DRE | 2238457 |
| CO Springs Fire | Original | D | 11/18/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2238151 |
| CO Springs Hazmat | Original | D | 11/18/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2238150 |
| CSU Water | Original | D | 11/18/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and revise the meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form (as needed). Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. PSD | PDosch | CSU Water | 2238079 |
| CSU Waste Water | Original | D | 11/18/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Waste Water | 2238078 |
| Gas/Elec. Utils | Original | D | 11/18/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | Gas/Elec. Utils | 2238071 |
| Zoning/Planning | Original | / | 11/18/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2237846 |
| CSU Contract Admin. | Original | D | 11/17/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2237825 |
| Construction | Original | D | 11/17/2025 | SHELLEY | SHELLEY | See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2237807 |
| Energy | Original | / | 11/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2237748 |
| Electronic Plan | Original | / | 11/11/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2235164 |
| Enumeration | Original | D | 11/10/2025 | BRENT | BRENT | Enumerations approval pending receipt in our office of a copy of the final recorded plat for Epicenter 2 filing no. 1. in our records. Enumerations approval pending issuance of wrecking permits for all existing buildings in this projects location. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2235087 |
| Electronic Plan | Original | / | 11/10/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2235021 |
| | Original | / | 11/10/2025 | SYSTEM | SYSTEM | Plan Review fees paid 11/10/2025 for plan submitted 10/29/2025. Submit Date updated to now. Plan now open for review. | | | 2235004 |
| Energy | Original | / | 10/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2230378 |
| Floodplain | Original | N | 10/29/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418323034) | | Floodplain | 2230377 |