| CO Springs Hazmat | Original | D | 11/26/2025 | CSFIRE | CSFIRE | See medical gas comments on the plumbing plans. Provide a written response as to how they have been addressed and resubmit plans and supplemental information.
CSFD Record Number: DFM-C-CG-25-00049 | smitty91 | CO Springs Hazmat | 2241763 |
| CO Springs Fire | Original | A | 11/17/2025 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2237557 |
| Energy | Original | D | 11/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2236627 |
| Electrical | Original | D | 11/14/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2236625 |
| Plumbing | Original | D | 11/11/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See clouded sections on additional requirements for 2021 IECC block. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data may be calculated from point of connection. See clouded sections on additional requirements for 2021 IECC block. P110, P210: Provide general notes that apply to the plumbing scope only. CW and HW do not match plumbing legend and abbreviations. ABV not shown on plumbing legend and abbreviations. All plumbing fixtures must be scheduled with manufacturer model numbers per PPRBD plan review requirements. Remove all fixtures from the fixture schedule that do not apply to the current plumbing scope. Provide automatic balancing valve (ABV?) manufacturer model numbers. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2235138 |
| Mechanical | Original | D | 11/10/2025 | TREVORH | TREVORH | Disapproved; Need to provide Fire and Fire smoke enlarged installation details on sheet M701and label all required dampers. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2235117 |
| CSU Water | Original | N | 11/10/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2235105 |
| CSU Waste Water | Original | N | 11/10/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2235104 |
| Construction | Original | A | 11/10/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2235033 |
| Energy | Original | N | 11/10/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2235032 |
| Electronic Plan | Original | / | 11/10/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2234788 |
| Enumeration | Original | N | 10/31/2025 | BECKYA | BECKYA | | | Enumeration | 2231294 |
| Electronic Plan | Original | / | 10/31/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2231283 |
| | Original | / | 10/30/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/30/2025 for plan submitted 10/30/2025. Submit Date updated to now. Plan now open for review. | | | 2231022 |
| Energy | Original | / | 10/30/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2231021 |
| Floodplain | Original | N | 10/30/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6408423013) | | Floodplain | 2231020 |