| Energy | Original | D | 12/19/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2250250 |
| Electrical | Original | D | 12/19/2025 | BERTHA | BERTHA | Pending Construction review - see Construction review comments.
Panel C is overloaded
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2250249 |
| Cherokee Water | Original | D | 11/26/2025 | CHEROKEEMETRO | CHEROKEEMETRO | Backflow prevention assembly and meter cannot be in crawl space. Need to be in building/unit | bzembles | Cherokee Water | 2241821 |
| Cherokee Waste Water | Original | A | 11/26/2025 | CHEROKEEMETRO | CHEROKEEMETRO | | bzembles | Cherokee Waste Water | 2241820 |
| County Zoning | Original | D | 11/20/2025 | DSDDEAN2 | DSDDEAN2 | Planning and Community Development file number TU2439 does not expire until May of 2026. Please resubmit for extension of the temp use closer to the expiration date and clearly show on the plans where the temp use trailer is located, so as not to confuse the plan with the current Site Development Plan that is in review at file number PPR2441. | | County Zoning | 2239436 |
| Zoning/Planning | Original | / | 11/18/2025 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2238108 |
| Mechanical | Original | D | 11/18/2025 | TREVORH | TREVORH | CURRENTLY Pending Construction review comments and scope of work clarification . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2238072 |
| Plumbing | Original | A | 11/18/2025 | SHANEN | SHANEN | | | Plumbing | 2237884 |
| Gas/Elec. Utils | Original | D | 11/17/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | Gas/Elec. Utils | 2237688 |
| Construction | Original | D | 11/17/2025 | BPHILLIPS | BPHILLIPS | Clarify proposed work scope * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2237635 |
| Electronic Plan | Original | / | 11/17/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2237503 |
| Electronic Plan | Original | / | 11/11/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2235360 |
| Enumeration | Original | N | 11/11/2025 | BECKYA | BECKYA | | | Enumeration | 2235344 |
| Enumeration | Original | D | 11/11/2025 | BECKYA | BECKYA | Permits have been issued for 554 & 560 Air Lane, but no building inspections have been performed. Please clarify scope. What is meant by connect to utilities? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2235257 |
| Electronic Plan | Original | / | 11/11/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2235133 |
| | Original | / | 11/10/2025 | SYSTEM | SYSTEM | Plan Review fees paid 11/10/2025 for plan submitted 11/10/2025. Submit Date updated to now. Plan now open for review. | | | 2235123 |
| Hazmat | Original | / | 11/10/2025 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2235112 |
| Fire | Original | / | 11/10/2025 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2235113 |
| Energy | Original | / | 11/10/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2235111 |
| Floodplain | Original | N | 11/10/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5408001028) | | Floodplain | 2235110 |