| Electrical | Original | D | 1/30/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2261699 |
| Electronic Plan | Original | / | 1/30/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2261659 |
| CO Springs Hazmat | Original | D | 1/29/2026 | CSFIRE | CSFIRE | Unsure how original hazmat comments were addressed. Please provide a written response as to how all hazmat comments were addressed. | smitty91 | CO Springs Hazmat | 2261205 |
| CO Springs DRE | Original | A | 1/29/2026 | SSADLER | SSADLER | Previous approval comments still apply.
Interior remodel only. No change in footprint, No change in parking. No change in occupancy. | | CO Springs DRE | 2261064 |
| CO Springs Fire | Original | D | 1/28/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2260757 |
| Plumbing | Original | D | 1/28/2026 | SHANEN | SHANEN | All plumbing fixtures must be scheduled with manufacturer model numbers (may be noted as "or equal" if owner provided). All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2260645 |
| Zoning/Planning | Original | / | 1/27/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2260565 |
| Construction | Original | D | 1/27/2026 | JUSTINL | JUSTINL | See life safety plan and G-002 for review comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2260561 |
| Electronic Plan | Original | / | 1/27/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2260399 |
| Submittal 2 | Original | / | 1/27/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2260229 |
| Electrical | Original | D | 12/19/2025 | BERTHA | BERTHA | Service is overloaded. Service 4 of 5 is rated for 600A.
Available fault current exceeds the withstand rating - ATS
Provide all required information for new (replaced) panels - one-line, fault current information, panel schedule, etc.
Provide panel and circuit number on all electrical equipment (new and relocated) on the power/lighting plans
Provide fault current information for all new air conditioning / refrigeration equipment. - RTU, CU, etc.
Pending Mechanical review of equipment - see mechanical review comments.
Incomplete review. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2250398 |
| CO Springs Hazmat | Original | D | 12/19/2025 | CSFIRE | CSFIRE | CSFD Record Number: DFM-C-HM-25-00041
See comments on the HMIS and Architectural Drawings. | smitty91 | CO Springs Hazmat | 2250174 |
| Mechanical | Original | D | 12/18/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2249870 |
| CO Springs Fire | Original | D | 12/18/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2249777 |
| CO Springs DRE | Original | A | 12/17/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Commercial interior remodel. No change of use or occupancy. Remodel of office space. | | CO Springs DRE | 2249306 |
| Zoning/Planning | Original | / | 12/17/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2249289 |
| Electronic Plan | Original | / | 12/17/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2248250 |
| CSU Water | Original | N | 12/16/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2248165 |
| CSU Waste Water | Original | N | 12/16/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2248161 |
| Plumbing | Original | D | 12/16/2025 | TCRIPPEN | TCRIPPEN | Disapproved pending construction * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2248089 |
| Zoning/Planning | Original | / | 12/16/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2248024 |
| Construction | Original | D | 12/16/2025 | JUSTINL | JUSTINL | See code study, life safety plan and architectural sheets for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2248017 |
| Energy | Original | N | 12/15/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2247750 |
| Electronic Plan | Original | / | 12/15/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2247359 |
| Enumeration | Original | N | 12/10/2025 | BECKYA | BECKYA | | | Enumeration | 2245862 |
| Electronic Plan | Original | / | 12/10/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2245852 |
| | Original | / | 12/9/2025 | SYSTEM | SYSTEM | Plan Review fees paid 12/09/2025 for plan submitted 12/09/2025. Submit Date updated to now. Plan now open for review. | | | 2245757 |
| Energy | Original | / | 12/9/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2245748 |
| Floodplain | Original | N | 12/9/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6429401065) | | Floodplain | 2245747 |