| CO Springs Fire | Original | D | 1/27/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account.
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | Jacob.Watson | CO Springs Fire | 2260326 |
| CO Springs DRE | Original | D | 1/22/2026 | SSADLER | SSADLER | Previous comments not addressed. Upload the approved and stamped development plan Upload the approval letter. Upload the final recorded plat Upload the final approved landscaping and irrigations plans Assurances for all private improvements must be posted All citywide impact fees must be paid. | | CO Springs DRE | 2258679 |
| EPC Health Dept | Original | D | 1/20/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2258005 |
| Energy | Original | D | 1/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2257992 |
| Mechanical | Original | A | 1/20/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2257991 |
| City Engr | Original | D | 1/20/2026 | HVO | HVO | Please see previous comment | | City Engr | 2257969 |
| Zoning/Planning | Original | / | 1/20/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2257951 |
| Electrical | Original | D | 1/20/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2257929 |
| Plumbing | Original | D | 1/20/2026 | SHANEN | SHANEN | Construction review comments must be addressed. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, sand/oil interceptor location, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. EWC-1 does not comply with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2257871 |
| CSU Water | Original | D | 1/20/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 2257850 |
| CSU Waste Water | Original | D | 1/20/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2257849 |
| Gas/Elec. Utils | Original | D | 1/20/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2257848 |
| Construction | Original | D | 1/20/2026 | DOUGC | DOUGC | Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2257810 |
| Enumeration | Original | D | 1/16/2026 | BRENT | BRENT | Enumerations approval pending receipt of a copy of the final recorded plat for Powers Autopark Filing No. 20. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2257154 |
| Electronic Plan | Original | / | 1/16/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2257142 |
| CSU Contract Admin. | Original | A | 1/16/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid. AMS | ASweet | CSU Contract Admin. | 2257140 |
| Submittal 2 | Original | / | 1/16/2026 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2257080 |
| CO Springs Fire | Original | D | 12/31/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2252696 |
| CO Springs Hazmat | Original | D | 12/31/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2252695 |
| Energy | Original | D | 12/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2251575 |
| Mechanical | Original | D | 12/29/2025 | TREVORH | TREVORH | Disapproved; Need a completed design of the vehicle exhaust system to include details , schedule new exhaust, include system on the balance and ventilation schedules. this design can be a completed by a separate mechanical Engineer , this will need coordinated by the Architect . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2251574 |
| Electronic Plan | Original | / | 12/29/2025 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2251472 |
| Plumbing | Original | D | 12/29/2025 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, sand/oil interceptor location, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Remove all references to mechanical contractor as a licensed plumbing contractor must perform all plumbing scope in this jurisdiction. Occupant load in excess of 15 occupants requires compliance with section 410.Show location of and piping for the required drinking fountain. Provide overflow scupper opening dimensions to verify compliance with section 1108.3. All condensate piping related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. Clarify how LW-1 and LW-2 are in compliance with section 1003.6. Schedule required drinking fountain. Clarify ORD-1 as secondary roof drainage is via overflow scuppers per sheet P1.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2251457 |
| Electrical | Original | D | 12/26/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2251336 |
| Electronic Plan | Original | / | 12/26/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2251291 |
| Elevators | Original | N | 12/26/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2251264 |
| EPC Health Dept | Original | D | 12/26/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2251196 |
| CSU Contract Admin. | Original | D | 12/23/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2251119 |
| Gas/Elec. Utils | Original | D | 12/23/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | Gas/Elec. Utils | 2251061 |
| CSU Water | Original | D | 12/23/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. SSH | SHillman | CSU Water | 2251064 |
| CSU Waste Water | Original | D | 12/23/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Waste Water | 2251063 |
| CO Springs DRE | Original | D | 12/23/2025 | SSADLER | SSADLER | Upload the final approved and stamped development plan Upload the approval letter Upload the final recorded plat Upload the final approved landscaping and irrigation plans Assurances for all private improvements must be posted Citywide impact fees must be paid. | | CO Springs DRE | 2251037 |
| City Engr | Original | D | 12/23/2025 | HVO | HVO | Please include a copy of the approved Development Plan, a copy of the approved Stormwater Enterprise approved Grading & Erosion Control Plan, and a copy of the approved Stormwater Enterprise approved Permanent Control Measures in the electronic building permit set | | City Engr | 2251036 |
| Zoning/Planning | Original | / | 12/23/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2251034 |
| Construction | Original | D | 12/23/2025 | DOUGC | DOUGC | CSF // LSP // Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2251002 |
| Electronic Plan | Original | / | 12/23/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2250973 |
| Enumeration | Original | D | 12/11/2025 | BRENT | BRENT | Include a site plan showing the building on the parcel and the access in the architectural plan pages. The DP plan pages show a trash enclosure. Include an elevation for the trash enclosure in the architectural plan pagas. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2246798 |
| Electronic Plan | Original | / | 12/11/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2246791 |
| | Original | / | 12/11/2025 | SYSTEM | SYSTEM | Plan Review fees paid 12/11/2025 for plan submitted 12/11/2025. Submit Date updated to now. Plan now open for review. | | | 2246721 |
| Energy | Original | / | 12/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2246702 |
| Floodplain | Original | N | 12/11/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6311100009) | | Floodplain | 2246701 |