| Electrical | Original | D | 1/30/2026 | BERTHA | BERTHA | Clarify if the new generator is being installed.
Pending CSFD review / approval. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2261893 |
| Energy | Original | D | 1/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2261894 |
| Electronic Plan | Original | / | 1/30/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2261665 |
| CO Springs Fire | Original | D | 1/26/2026 | CSFIRE | CSFIRE | Comments from previous reviews has not been addressed.
You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2259631 |
| CO Springs Hazmat | Original | D | 1/26/2026 | CSFIRE | CSFIRE | Provide hazmat triage forms for new & demoed generators | chiptaylor | CO Springs Hazmat | 2259630 |
| | Original | / | 1/23/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2259430 |
| | Original | / | 1/23/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2259383 |
| Submittal 3 | Original | / | 1/23/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2259382 |
| Energy | Original | D | 1/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2255406 |
| Electrical | Original | D | 1/12/2026 | BERTHA | BERTHA | Comply with previous review comment - Provide all panel schedules affected by the scope of work.
Comply with previous review comment - Provide volt amps on all branch circuits and calculated load of panel in amps
Comply with previous review comment - Verify compliance with Table 310.16
Comply with previous review comment - Provide Fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed .
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2255405 |
| Electronic Plan | Original | / | 1/12/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2255091 |
| CO Springs Fire | Original | D | 1/9/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account.
Previous disapproval comments concerning hazmat forms for new and demolished generators was not addressed. | chiptaylor | CO Springs Fire | 2254943 |
| CO Springs Hazmat | Original | D | 1/9/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2254942 |
| Submittal 2 | Original | / | 1/8/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2254903 |
| Electrical | Original | D | 12/18/2025 | BERTHA | BERTHA | Provide all panel schedules affected by the scope of work.
Provide volt amps on all branch circuits and calculated load of panel in amps
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
Verify compliance with Table 310.16
Provide Fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Verify distribution equipment - see drawing note 14 page E3.1
Verify gear being fed - see drawing note 3 page E3.2
Provide location of existing 2000AMP ATS
Complete re-review necessary. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2249944 |
| Energy | Original | D | 12/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2249945 |
| Elevators | Original | N | 12/18/2025 | ROBERTV | ROBERTV | No scope of work affecting the elevators after the existing mainline disconnects | | Elevators | 2249890 |
| CO Springs Fire | Original | D | 12/16/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2247869 |
| CO Springs Hazmat | Original | D | 12/16/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2247868 |
| Electronic Plan | Original | / | 12/15/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2247631 |
| CSU Water | Original | N | 12/15/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2247613 |
| CSU Waste Water | Original | N | 12/15/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2247612 |
| Mechanical | Original | N | 12/15/2025 | TCRIPPEN | TCRIPPEN | No mechanical scope | | Mechanical | 2247601 |
| Plumbing | Original | N | 12/15/2025 | SHANEN | SHANEN | No plumbing scope indicated. | | Plumbing | 2247572 |
| Construction | Original | A | 12/15/2025 | SHELLEY | SHELLEY | | | Construction | 2247565 |
| Electronic Plan | Original | / | 12/15/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2247513 |
| Enumeration | Original | N | 12/12/2025 | AMY | AMY | | | Enumeration | 2247067 |
| Electronic Plan | Original | / | 12/12/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2247050 |
| | Original | / | 12/12/2025 | SYSTEM | SYSTEM | Plan Review fees paid 12/12/2025 for plan submitted 12/11/2025. Submit Date updated to now. Plan now open for review. | | | 2246883 |
| Energy | Original | / | 12/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2246805 |
| Floodplain | Original | N | 12/11/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7322402001) | | Floodplain | 2246804 |