| CO Springs Fire | Original | D | 1/29/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2261351 |
| CO Springs Hazmat | Original | D | 1/29/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2261350 |
| Mechanical | Original | D | 1/28/2026 | TREVORH | TREVORH | Disapproved; Preliminary Review Need to see elevator and construction comments addressed to continue with the Mechanical reviewif possible Need to turn off colors and clouds on plans , black and white are sufficient * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2260861 |
| Enumeration | Original | D | 1/27/2026 | BERTHA | BERTHA | Provide compliance with 230.95
Provide footprint (site plan) showing all electrical service equipment and disconnects serving the structure
Provide all conductor size, type and quantity.
Provide elevator horsepower on the one line.
Provide elevator feeder size, type, and quantity on the one line.
Provide elevator over current device size ( Ampacity) on the one line.
Pending approval in Elevators - see Elevator review comments
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2260494 |
| CO Springs DRE | Original | D | 1/27/2026 | SSADLER | SSADLER | Disapproved. The City is currently in receipt of two appeals for this development. In accordance with UDC Section 7.5.415.A.5 Stay of Decisions, no building permits shall be issued nor shall construction commence until final decisions are rendered by City Council. City Planning staff may have addition comments or corrections once review commences. All assurances and impact fees shall also be posted prior to building permit issuance.
Upload the following documents: 1. final recorded plat 2. final approved landscaping and irrigation plans.
Assurances for all private improvements must be posted prior to building permit issuance Citywide impact fees must be paid prior to building permit issuance | | CO Springs DRE | 2260363 |
| Plumbing | Original | D | 1/26/2026 | SHANEN | SHANEN | Preliminary review. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Construction review comments regarding occupancy and occupant load must be addressed to verify compliance with section 403.1. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Plumbing scope shall comply with 2021 IECC. Clarify how SP-1 is in compliance with section 301.6. Exception. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Sleeves shall comply with section 305.3. Show all plumbing fixtures on the backgrounds and not just the abbreviation for the fixture. Clarify how laundry washers are in compliance with section 1003.6. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Correct all illegible text. Controls and hand showers shall comply with ICC A117.1-2017 section 608.4. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Provide required CSU variance letter for the indoor sand/oil interceptor. Contact Robert Bowren at 719-668-1735 or fog@csu.org. Lavatories must show compliance with 2021 IECC section C404.5.1. Water heater detail must show compliance with IECC section C404.3. Provide a piping materials schedule on the plumbing plans per PPRBD plan review requirements. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2259738 |
| Electronic Plan | Original | / | 1/26/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2259681 |
| Elevators | Original | D | 1/23/2026 | ROBERTV | ROBERTV | Need site specific shop drawings and power data for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
Also See Sheets: A403, A404, M201, E201, E202, E301, E601 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2259545 |
| City Engr | Original | D | 1/22/2026 | HVO | HVO | Please include a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan, and a copy of the approved Stormwater Enterprise approved Permanent Control Measures in the electronic building permit set | | City Engr | 2258922 |
| CSU Water | Original | D | 1/22/2026 | CSUREVIEW | CSUREVIEW | CSU-approved wastewater and water mainline Construction Drawings (CD's) and CSU-approved Utility Service Plan (USP) must be attached to the permit set. Call UDS at 719-668-8259 with questions. SSH | SHillman | CSU Water | 2258789 |
| CSU Waste Water | Original | D | 1/22/2026 | CSUREVIEW | CSUREVIEW | CSU-approved wastewater and water mainline Construction Drawings (CD's) and CSU-approved Utility Service Plan (USP) must be attached to the permit set. Call UDS at 719-668-8259 with questions. SSH | SHillman | CSU Waste Water | 2258787 |
| Gas/Elec. Utils | Original | A | 1/22/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2258783 |
| CSU Contract Admin. | Original | D | 1/22/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. AMS | ASweet | CSU Contract Admin. | 2258717 |
| Zoning/Planning | Original | / | 1/22/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2258652 |
| Construction | Original | D | 1/22/2026 | SHELLEY | SHELLEY | Too many items. See plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2258633 |
| Electronic Plan | Original | / | 1/21/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2258451 |
| Enumeration | Original | D | 1/7/2026 | BRENT | BRENT | Show the dimensions of the trash enclosure. Trash enclosures over 7 feet in height require a separate address and building permit. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2254344 |
| Enumeration | Original | A | 12/17/2025 | BRENT | BRENT | | | Enumeration | 2249330 |
| Electronic Plan | Original | / | 12/17/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2249303 |
| | Original | / | 12/17/2025 | SYSTEM | SYSTEM | Plan Review fees paid 12/17/2025 for plan submitted 12/12/2025. Submit Date updated to now. Plan now open for review. | | | 2249297 |
| Energy | Original | / | 12/12/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2247030 |
| Floodplain | Original | N | 12/12/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6209303002) | | Floodplain | 2247029 |