| Cherokee Water | Original | D | 2/3/2026 | CHEROKEEMETRO | CHEROKEEMETRO | Refer to plumbing plan notes | bzembles | Cherokee Water | 2263112 |
| Cherokee Waste Water | Original | D | 2/3/2026 | CHEROKEEMETRO | CHEROKEEMETRO | Refer to plumbing plan notes | bzembles | Cherokee Waste Water | 2263111 |
| Energy | Original | D | 1/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2254442 |
| Electrical | Original | D | 1/7/2026 | CONNERM | CONNERM | Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC). The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide location of all service equipment feeding the structure (meter).
Comply with 230.2
Provide room names on electrical plans
Preliminary review only. Pending construction review and approval. See construction review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2254441 |
| Mechanical | Original | D | 1/7/2026 | TCRIPPEN | TCRIPPEN | Disapproved see constructions notes * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2254333 |
| County Zoning | Original | D | 1/7/2026 | DSDBENSON2 | DSDBENSON2 | There is no Site Development Plan on file with the El Paso County Planning and Community Development Department. Contact Miranda Benson at 719-520-7940 or MirandaBenson2@elpasoco.com to get this project set up. Thank you. | | County Zoning | 2254245 |
| Electronic Plan | Original | / | 1/7/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2254179 |
| Gas/Elec. Utils | Original | D | 1/7/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2254121 |
| Zoning/Planning | Original | / | 1/7/2026 | DSDBENSON2 | DSDBENSON2 | In Current Review by DSDBENSON2 | | Zoning/Planning | 2254022 |
| Plumbing | Original | D | 1/7/2026 | SHANEN | SHANEN | Construction review comments must be addressed to verify compliance with section 403 and 404. Clarify how restroom locations are compliant with section 403.3.1. All condensate piping related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2253989 |
| Construction | Original | D | 1/6/2026 | JUSTINL | JUSTINL | Preliminary review only see code study, architectural, life safety, structural, metal building and IECC documents for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2253979 |
| Electronic Plan | Original | / | 1/6/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2253887 |
| Enumeration | Original | A | 1/6/2026 | AMY | AMY | The address change is complete and will be mailed out tomorrow. The new address is 551 Hathaway Drive. All of the sheets of this plan have been changed to this address. If any of the sheets get changed out, correct the address. | | Enumeration | 2253846 |
| Enumeration | Original | D | 12/18/2025 | AMY | AMY | The zip code for this area is 80915 not 80903. Corrected on the Code Study form. Both structures on site are under the same address. By added a building letter to the address will not do and is not allowed. By today’s standards each commercial structure requires a separate address. Which building would the owner like to keep as 555 Hathaway Drive? The other one will change. Here is this link is the information Enumeration needs to change one of the addresses. https://www.pprbd.org/File/Resources/Downloads/Addressing/Request%20for%20change%20of%20address%20ACCESS.pdf * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2249801 |
| Electronic Plan | Original | / | 12/18/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2249759 |
| | Original | / | 12/17/2025 | SYSTEM | SYSTEM | Plan Review fees paid 12/17/2025 for plan submitted 12/15/2025. Submit Date updated to now. Plan now open for review. | | | 2249625 |
| Fire | Original | / | 12/15/2025 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2247688 |
| Hazmat | Original | / | 12/15/2025 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2247687 |
| Energy | Original | / | 12/15/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2247686 |
| Floodplain | Original | N | 12/15/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5407400093) | | Floodplain | 2247685 |