| Energy | Original | D | 2/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2264685 |
| Mechanical | Original | D | 2/9/2026 | TREVORH | TREVORH | Disapproved; Need to include Natural Gas plan in this submittal package,include pipe material, sizing, meter location andwhat table was used in the 2021 IFGC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2264684 |
| Plumbing | Original | D | 2/4/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Elevator sump discharge must show compliance with section 301.6 Exception. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. ST-5 /12 for residential use only per manufacturer. Provide gpm and/or square footage served by each component of the roof drainage system. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2263174 |
| Electrical | Original | D | 2/4/2026 | BERTHA | BERTHA | Preliminary review only
Provide all conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work - clearly indicate number of sets - comply with 310.16
Provide all overcurrent protection for MCB and feeders on the one-line
Provide listed series rated combinations.
Pending approval in Elevators - see Elevator review comments
Provide elevator horsepower on the one line.
Provide elevator feeder size, type, and quantity on the one line.
Provide elevator over current device size ( Ampacity) on the one line.
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Comply with 110.26(C)
Provide footprint (site plan) clearly showing all electrical service equipment and disconnects serving the structure
Homogenize equipment labels e.g., Powerwall vs Prefabricated Distribution Center.
Comply with the currently adopted 2021 IECC
Complete re-review necessary. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2263115 |
| Elevators | Original | D | 2/3/2026 | ROBERTV | ROBERTV | Need site specific shop drawings and power data for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
Also see sheets: A1.0, A7.3a, A7.4a, A7.4b, H1.0, H1.1, E3.0A, P1.0, P2.0, P2.1 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2263109 |
| CO Springs Fire | Original | D | 1/28/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2260934 |
| CO Springs Hazmat | Original | D | 1/28/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2260933 |
| CO Springs DRE | Original | D | 1/21/2026 | SSADLER | SSADLER | Upload the final approved and stamped development plan. Upload the final landscaping and irrigation plans. Upload the approval letter that allows for the addition.
Once review is complete, there may be fees and assurances that are due prior to building permit issuancse | | CO Springs DRE | 2258382 |
| City Engr | Original | D | 1/20/2026 | HVO | HVO | Please include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2257971 |
| CSU Water | Original | D | 1/20/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2257567 |
| Gas/Elec. Utils | Original | D | 1/20/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2257566 |
| CSU Waste Water | Original | D | 1/20/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2257565 |
| Gas/Elec. Utils | Original | A | 1/20/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 2257563 |
| Zoning/Planning | Original | / | 1/20/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2257548 |
| Construction | Original | D | 1/20/2026 | JUSTINL | JUSTINL | Preliminary review only. Need to address building height and area comments as there is an AM&M that was not followed, incorrect code section references to open/covered malls and anchor stores ( which this is not ). Need clarification on my uses of spaces to determine occupancy classifications for function of spaces. See code study form, architectural, structural plans for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2257521 |
| Energy | Original | / | 1/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2255954 |
| Electronic Plan | Original | / | 1/12/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2255279 |
| Enumeration | Original | D | 1/5/2026 | BRENT | BRENT | The suite number for this new tenant space is 140. Show this suite number anywhere the address appears in the plan pages and the code study form. Include a more detailed site plan in the architectural plan pages which shows all tenant spaces in this building, with addressing shown. The north arrow appears to be incorrect on multiple plan pages. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2253387 |
| Electronic Plan | Original | / | 12/29/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2251614 |
| | Original | / | 12/29/2025 | SYSTEM | SYSTEM | Plan Review fees paid 12/29/2025 for plan submitted 12/19/2025. Submit Date updated to now. Plan now open for review. | | | 2251461 |
| Energy | Original | / | 12/19/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2250375 |
| Floodplain | Original | N | 12/19/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308303032) | | Floodplain | 2250373 |