| CO Springs Fire | Original | A | 2/5/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2263858 |
| CO Springs Hazmat | Original | N | 2/5/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2263857 |
| Energy | Original | D | 2/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2262407 |
| Mechanical | Original | D | 2/2/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2262406 |
| Electronic Plan | Original | / | 2/2/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2262339 |
| Gas/Elec. Utils | Original | A | 1/30/2026 | CSUREVIEW | CSUREVIEW | Per discussions with field engineer, the existing electric meter can support the new load and does not need to be replaced. Reach out to Josh Hoepfner at 719-668-3242 with an questions. SSH | SHillman | Gas/Elec. Utils | 2261617 |
| CSU Water | Original | N | 1/30/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2261584 |
| CSU Waste Water | Original | N | 1/30/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2261582 |
| CO Springs DRE | Original | A | 1/30/2026 | SSADLER | SSADLER | Interior remodel only. No change in footprint, No change in parking. No change in occupancy. | | CO Springs DRE | 2261463 |
| Electrical | Original | D | 1/29/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2261414 |
| Energy | Original | / | 1/29/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2261413 |
| Electronic Plan | Original | / | 1/29/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2261393 |
| Zoning/Planning | Original | / | 1/29/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2261257 |
| Plumbing | Original | D | 1/29/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide a piping materials schedule on the plumbing plans. All new fixtures must be scheduled with manufacturer model numbers on the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data may be calculated from the point of connection. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Remove all references to the mechanical scope from the demolition general notes. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2261254 |
| Construction | Original | D | 1/29/2026 | JUSTINL | JUSTINL | See code study, Life safety, architectural and structural plans for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2261220 |
| Energy | Original | N | 1/27/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2260293 |
| Electronic Plan | Original | / | 1/26/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2260083 |
| Enumeration | Original | N | 1/8/2026 | BECKYA | BECKYA | | | Enumeration | 2254938 |
| Electronic Plan | Original | / | 1/8/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2254870 |
| | Original | / | 1/8/2026 | SYSTEM | SYSTEM | Plan Review fees paid 01/08/2026 for plan submitted 12/31/2025. Submit Date updated to now. Plan now open for review. | | | 2254862 |
| Energy | Original | / | 12/31/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2252607 |
| Floodplain | Original | N | 12/31/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6332401007) | | Floodplain | 2252606 |