| Electrical | Original | D | 1/28/2026 | CONNERM | CONNERM | Recessed lighting must comply with C402.5.10.
Controlled receptacles must be shown on the plan per 2021 IECC C405.11 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2260715 |
| Mechanical | Original | D | 1/27/2026 | TREVORH | TREVORH | Disapproved; Need to indicate the allowable amounts, calculations are showing "Does Not comply"Are sensors and alarms being planned for if so include in keyed Notes. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2260637 |
| Electronic Plan | Original | / | 1/27/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2260383 |
| County Zoning | Original | N | 1/27/2026 | DSDPARSONS | DSDPARSONS | Updating the windows, doors and office building I-2 zoned same type of use as existing. | | County Zoning | 2260143 |
| Zoning/Planning | Original | / | 1/27/2026 | DSDPARSONS | DSDPARSONS | In Current Review by DSDPARSONS | | Zoning/Planning | 2260139 |
| Zoning/Planning | Original | / | 1/27/2026 | DSDKILGORE | DSDKILGORE | In Current Review by DSDKILGORE | | Zoning/Planning | 2260123 |
| Plumbing | Original | D | 1/27/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See clouded sections on additional requirements for 2021 IECC block. All gas piping and condensate piping related items shall be on the mechanical plans.Remove all references to gas piping and condensate piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Provide a water heater installation detail. Detail must show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. ST-5 is for residential use only per manufacturer. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. Cleanouts shall comply with section 708. Cleanout sizing shall comply with section 708.1.5. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2260111 |
| Construction | Original | D | 1/26/2026 | JUSTINL | JUSTINL | See architectural plans for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2260048 |
| Energy | Original | N | 1/26/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2259965 |
| Electronic Plan | Original | / | 1/23/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2259253 |
| Enumeration | Original | N | 1/23/2026 | AMY | AMY | | | Enumeration | 2258985 |
| Electronic Plan | Original | / | 1/23/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2258983 |
| | Original | / | 1/22/2026 | SYSTEM | SYSTEM | Plan Review fees paid 01/22/2026 for plan submitted 01/22/2026. Submit Date updated to now. Plan now open for review. | | | 2258972 |
| Fire | Original | / | 1/22/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2258804 |
| Hazmat | Original | / | 1/22/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2258803 |
| Energy | Original | / | 1/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2258802 |
| Floodplain | Original | N | 1/22/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5406305006) | | Floodplain | 2258801 |