| CO Springs DRE | Original | A | 3/13/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2279711 |
| Plumbing | Original | D | 3/12/2026 | SHANEN | SHANEN | Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc.Calculations may be taken from the point of connection. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2279203 |
| Electrical | Original | A | 3/12/2026 | CONNERM | CONNERM | | | Electrical | 2279174 |
| Zoning/Planning | Original | / | 3/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2279167 |
| Construction | Original | A | 3/12/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2279155 |
| Electronic Plan | Original | / | 3/12/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2279099 |
| Enumeration | Original | N | 3/10/2026 | BECKYA | BECKYA | | | Enumeration | 2278060 |
| Submittal 2 | Original | / | 3/10/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2278015 |
| CO Springs Fire | Original | D | 2/27/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2274242 |
| CO Springs Hazmat | Original | N | 2/27/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2274241 |
| Mechanical | Original | A | 2/25/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2270717 |
| CO Springs DRE | Original | A | 2/24/2026 | SSADLER | SSADLER | Interior remodel only. No change in footprint, No change in parking. No change in occupancy. | | CO Springs DRE | 2270111 |
| Electrical | Original | D | 2/20/2026 | CONNERM | CONNERM | Recessed lighting must comply with C402.5.10
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2269079 |
| Electronic Plan | Original | / | 2/20/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2269043 |
| Plumbing | Original | D | 2/20/2026 | SHANEN | SHANEN | Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. State of Colorado registered EOR stamp/signature required. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to Wisconsin. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. Heated water supply piping must show compliance with 2021 IECC section C404.5. Lavatories must show compliance with 2021 IECC section C404.5.1. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data may be calculated from the point of connection. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2269014 |
| CSU Waste Water | Original | N | 2/19/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2268716 |
| CSU Water | Original | N | 2/19/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2268715 |
| Zoning/Planning | Original | / | 2/19/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2268706 |
| Construction | Original | D | 2/19/2026 | BPHILLIPS | BPHILLIPS | Life safety plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2268637 |
| Energy | Original | N | 2/19/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2268575 |
| Electronic Plan | Original | / | 2/18/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2268127 |
| Enumeration | Original | D | 1/26/2026 | BECKYA | BECKYA | Show all tenant spaces on the 2nd floor with addressing and area of work highlighted. Update the Code Study Form to show the correct Tax Schedule Number. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2259973 |
| Electronic Plan | Original | / | 1/26/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2259969 |
| | Original | / | 1/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 01/26/2026 for plan submitted 01/26/2026. Submit Date updated to now. Plan now open for review. | | | 2259870 |
| Energy | Original | / | 1/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2259703 |
| Floodplain | Original | N | 1/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6234406009) | | Floodplain | 2259702 |