| Energy | Original | D | 3/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2277813 |
| Electrical | Original | D | 3/9/2026 | CONNERM | CONNERM | Provide full panel demand calc or add panels HP1 and HP3 to "30 day metering report" note below
Add "Prior to final inspection" to the end of metering report note
Panels HP1, HP3, LTP3A still not shown on site plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2277812 |
| Electronic Plan | Original | / | 3/9/2026 | WHITNEYH | WHITNEYH | In Current Review by WHITNEYH | | Electronic Plan | 2277336 |
| Electronic Plan | Original | / | 3/9/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2277335 |
| Construction | Original | A | 3/6/2026 | SHELLEY | SHELLEY | | | Construction | 2277017 |
| Submittal 2 | Original | / | 3/6/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2276836 |
| CO Springs Fire | Original | A | 2/27/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2274231 |
| CO Springs Hazmat | Original | N | 2/27/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2274230 |
| Energy | Original | D | 2/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2270038 |
| Mechanical | Original | A | 2/23/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2270037 |
| Plumbing | Original | N | 2/20/2026 | SHANEN | SHANEN | No plumbing scope indicated. | | Plumbing | 2269017 |
| CSU Water | Original | N | 2/20/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2268989 |
| CSU Waste Water | Original | N | 2/20/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2268988 |
| Electrical | Original | D | 2/20/2026 | CONNERM | CONNERM | Show location and identify all electrical panels and equipment under scope of work on floor plan
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2268975 |
| Electronic Plan | Original | / | 2/20/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2268851 |
| Construction | Original | D | 2/20/2026 | SHELLEY | SHELLEY | See code study form and code data * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2268779 |
| Electronic Plan | Original | / | 2/20/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2268771 |
| Enumeration | Original | N | 1/29/2026 | BRENT | BRENT | | | Enumeration | 2261327 |
| Electronic Plan | Original | / | 1/29/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2261312 |
| | Original | / | 1/29/2026 | SYSTEM | SYSTEM | Plan Review fees paid 01/29/2026 for plan submitted 01/27/2026. Submit Date updated to now. Plan now open for review. | | | 2261210 |
| Energy | Original | / | 1/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2260162 |
| Floodplain | Original | N | 1/27/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6426118011) | | Floodplain | 2260161 |