| Energy | Original | A | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2285388 |
| Electrical | Original | A | 3/26/2026 | CONNERM | CONNERM | | | Electrical | 2285387 |
| Energy | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2285167 |
| Energy | Original | D | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2285166 |
| Electronic Plan | Original | / | 3/26/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2285163 |
| Mechanical | Original | A | 3/26/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2284967 |
| Construction | Original | A | 3/26/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2284868 |
| Submittal 2 | Original | / | 3/26/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2284829 |
| CO Springs Fire | Original | A | 3/9/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2277866 |
| CO Springs Hazmat | Original | N | 3/9/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2277864 |
| Energy | Original | D | 3/3/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2275060 |
| Mechanical | Original | A | 3/3/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2275059 |
| CSU Water | Original | N | 3/2/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2274665 |
| CSU Waste Water | Original | N | 3/2/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2274664 |
| Electrical | Original | D | 3/2/2026 | CONNERM | CONNERM | Fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
Recessed lighting must comply with C402.5.10
Panel labels on one-line do not match panel schedules * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2274640 |
| Plumbing | Original | A | 3/2/2026 | SHANEN | SHANEN | | | Plumbing | 2274597 |
| Electronic Plan | Original | / | 3/2/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2274555 |
| Construction | Original | D | 3/2/2026 | BPHILLIPS | BPHILLIPS | Life safety plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2274511 |
| Electronic Plan | Original | / | 2/24/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2270519 |
| Enumeration | Original | N | 2/13/2026 | BRENT | BRENT | | | Enumeration | 2266563 |
| Electronic Plan | Original | / | 2/13/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2266556 |
| | Original | / | 2/12/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/12/2026 for plan submitted 02/05/2026. Submit Date updated to now. Plan now open for review. | | | 2266214 |
| Energy | Original | / | 2/5/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2263724 |
| Floodplain | Original | N | 2/5/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418211011) | | Floodplain | 2263723 |