| Donald Wescott Hazmat (CSFD) | Original | D | 3/30/2026 | CSFIRE | CSFIRE | DFM-C-CG-26-00012 NEED med Gas Piping Plans NEED Compressed Gas Questionnaire Need Piping Specifications Sheets Need completed Medical Gas submittal per NFPA 99.
You must have an ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Technical Service staff to link the review to your account. | mark.stanwood@colora | Donald Wescott Hazmat (CSFD) | 2286362 |
| EPC Health Dept | Original | N | 3/12/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable. Per Nick Sallecchiam, Project Manager, earthmoving activities are < 1 acre. MLL | mlockwood | EPC Health Dept | 2279031 |
| Triview Water | Original | D | 3/10/2026 | TRIVIEWMETRO | TRIVIEWMETRO | Line is undersized for the WFSU provided. Please provide calculations supporting the fixture count provided, and include all equipment which uses water including sterilization equipment and water use for chair wands. Irrigation plan does not show connection to the water service at 790 Sky Vista. Please clarify whether the irrigation branch shown on entry detail will be tied into existing irrigation system (which is not shown on irrigation plan) or will be used for drip system, or if it is erroneous. Please use Colorado Springs Utilities 1” meter entry detail #B4-5.
DCW and fire were installed as separate service lines due to TMD inspector comments. Please update civil utility drawings to reflect this change. | rnortonTMD | Triview Water | 2278378 |
| Triview Waste Water | Original | D | 3/10/2026 | TRIVIEWMETRO | TRIVIEWMETRO | Please provide 2-way cleanout for sewer service at building junction.
Please provide details for amalgam separator on vacuum service. Amalgam separator will be required. | rnortonTMD | Triview Waste Water | 2278376 |
| Donald Wescott Fire (CSFD) | Original | D | 3/9/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | Donald Wescott Fire (CSFD) | 2277659 |
| EPC Health Dept | Original | D | 3/6/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2276846 |
| Energy | Original | D | 3/4/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2275858 |
| Electrical | Original | A | 3/4/2026 | BERTHA | BERTHA | | | Electrical | 2275857 |
| Gas/Elec. Utils | Original | D | 3/4/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. Not in Colorado Springs Utilities' gas service territory. MLW | mlwilliams | Gas/Elec. Utils | 2275699 |
| Mechanical | Original | D | 3/3/2026 | TREVORH | TREVORH | Disapproved; Need construction review comments addressed , Need to see the MECHcomCheck stamped and uploaded * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2275568 |
| Plumbing | Original | D | 3/3/2026 | SHANEN | SHANEN | EWC does not comply with section 410.3. 1" water distribution is undersized to serve 39.3 W.F.S.U. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Water service entry location does not match referenced civil plans. Show compliance with section 1108. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2275291 |
| Elevators | Original | N | 3/3/2026 | ANDREAL | ANDREAL | No Conveyance in this scope of work. | | Elevators | 2275233 |
| CSU Contract Admin. | Original | D | 3/3/2026 | CSUAPPSPRM | CSUAPPSPRM | Address is not in CSU service area.
AMS | ASweet | CSU Contract Admin. | 2275158 |
| Construction | Original | D | 3/3/2026 | BPHILLIPS | BPHILLIPS | Life safety plan, IECC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2275034 |
| Electronic Plan | Original | / | 2/27/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2274187 |
| Electronic Plan | Original | / | 2/24/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2270522 |
| Enumeration | Original | A | 2/11/2026 | BECKYA | BECKYA | | | Enumeration | 2265498 |
| Electronic Plan | Original | / | 2/11/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2265482 |
| | Original | / | 2/10/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/10/2026 for plan submitted 02/05/2026. Submit Date updated to now. Plan now open for review. | | | 2265297 |
| Waste Water Div | Original | / | 2/5/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2263740 |
| Water Division | Original | / | 2/5/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2263739 |
| Energy | Original | / | 2/5/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2263738 |
| Floodplain | Original | N | 2/5/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7136201016) | | Floodplain | 2263737 |