| Electrical | Original | D | 3/19/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2281973 |
| Construction | Original | A | 3/19/2026 | SHELLEY | SHELLEY | | | Construction | 2281943 |
| Enumeration | Original | N | 3/18/2026 | BRENT | BRENT | | | Enumeration | 2281560 |
| Electronic Plan | Original | / | 3/18/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2281555 |
| Submittal 2 | Original | / | 3/17/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2281342 |
| CO Springs Fire | Original | D | 3/10/2026 | CSFIRE | CSFIRE | DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments:
1. Provide what level EV chargers will be (1, 2, or 3) | Jacob.Watson | CO Springs Fire | 2278325 |
| CO Springs Hazmat | Original | D | 3/10/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2278324 |
| Mechanical | Original | A | 3/4/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2275821 |
| Electrical | Original | D | 3/4/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2275732 |
| Plumbing | Original | A | 3/4/2026 | SHANEN | SHANEN | | | Plumbing | 2275725 |
| Electronic Plan | Original | / | 3/4/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2275721 |
| CSU Water | Original | N | 3/4/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. No new water service outside of building. MDA | malcuran | CSU Water | 2275715 |
| CSU Waste Water | Original | N | 3/4/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2275714 |
| Construction | Original | A | 3/4/2026 | SHELLEY | SHELLEY | | | Construction | 2275705 |
| Energy | Original | N | 3/4/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2275700 |
| Electronic Plan | Original | / | 3/2/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2274771 |
| Enumeration | Original | D | 2/23/2026 | BRENT | BRENT | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2269719 |
| Electronic Plan | Original | / | 2/23/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2269708 |
| | Original | / | 2/23/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/23/2026 for plan submitted 02/10/2026. Submit Date updated to now. Plan now open for review. | | | 2269591 |
| Energy | Original | / | 2/10/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2265208 |
| Floodplain | Original | N | 2/10/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418324045) | | Floodplain | 2265207 |