| CO Springs DRE | Original | A | 3/30/2026 | SSADLER | SSADLER | Previous approval comments still apply. Approved for level 2 chargers and replacement of a few trees on the property. | | CO Springs DRE | 2286145 |
| Zoning/Planning | Original | / | 3/27/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2285662 |
| Enumeration | Original | A | 3/27/2026 | BECKYA | BECKYA | | | Enumeration | 2285617 |
| | Original | / | 3/27/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2285610 |
| | Original | / | 3/27/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2285603 |
| Submittal 3 | Original | / | 3/27/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2285602 |
| CO Springs DRE | Original | A | 3/26/2026 | SSADLER | SSADLER | Approved for level 2 charging stations. | | CO Springs DRE | 2284858 |
| Zoning/Planning | Original | / | 3/25/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2284603 |
| CO Springs Hazmat | Original | D | 3/17/2026 | CSFIRE | CSFIRE | CSFD Record Number: DFM-C-DC-26-00003
Provide a to-scale and/or dimensioned site plan with the following information:
Width of drive lanes on either side of charging stalls
Proposed landscaping around chargers
Locations of all chargers and equipment
Bollard protection of chargers
Emergency shut off location
Separations between charging and non charging stalls
Also contact City Planning as they will want a development plan amendment showing the proposed equipment and use. | smitty91 | CO Springs Hazmat | 2281153 |
| Electrical | Original | D | 3/13/2026 | BERTHA | BERTHA | Comply with previous review comment - Provide footprint (site plan) showing all electrical service equipment and disconnects, lighting, new panel board, etc. - Provide electrical site plan with design professionals stamp. Clearly indicate/label all equipment.
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations as it pertains to the scope of work. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide revised load summary - indicate all load - site lighting, new panelboard, etc.
Provide all panel schedules with volt amps on all branch circuits and calculated load of panel in amps
Provide complete electrical plans - see the following for Electrical Plan Review Requirements - https://www.pprbd.org/File/ByAlias/ElectricalReview
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2279923 |
| CO Springs Fire | Original | N | 3/9/2026 | CSFIRE | CSFIRE | No Fire Final
HAZ-MAT REVIEW REQUIRED Based upon the information provided, a hazardous materials review is required. Your plans have been forwarded to the HazMat reviewer. | Jacob.Watson | CO Springs Fire | 2277796 |
| Electronic Plan | Original | / | 3/4/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2276097 |
| Enumeration | Original | A | 3/2/2026 | BECKYA | BECKYA | | | Enumeration | 2274981 |
| Submittal 2 | Original | / | 3/2/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2274897 |
| Electrical | Original | D | 2/20/2026 | BERTHA | BERTHA | Provide NRTL Certification for Power Unit and Dispenser
Provide footprint (site plan) showing all electrical service equipment and disconnects . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2269136 |
| CO Springs Fire | Original | D | 2/20/2026 | CSFIRE | CSFIRE | DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review.
1. Provide what level EV chargers are (1, 2, or 3)
(DISAPPROVED) TEMPORARY ADDRESS A temporary address has been assigned to these plans. CSFD will not approve the construction plans until PPRBD Enumerations has assigned a permanent address to this facility and has approved the construction plans. | Jacob.Watson | CO Springs Fire | 2269104 |
| Enumeration | Original | D | 2/11/2026 | BRENT | BRENT | This new electric service will require a unique street address. Include a larger scale site plan showing the location of this new service relative to the buildings in this shopping center so that an accurate address can be assigned. Once a new address has been assigned, all plan pages and the code study form will need to be updated to show the assigned address. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2265751 |
| Electronic Plan | Original | / | 2/11/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2265743 |
| Electronic Plan | Original | / | 2/11/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2265685 |
| | Original | / | 2/11/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/11/2026 for plan submitted 02/11/2026. Submit Date updated to now. Plan now open for review. | | | 2265484 |
| Energy | Original | N | 2/11/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2265450 |
| Floodplain | Original | N | 2/11/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5330301005) | | Floodplain | 2265449 |