| CO Springs DRE | Original | A | 3/31/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No exterior changes | | CO Springs DRE | 2286799 |
| Energy | Original | D | 3/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2286587 |
| Mechanical | Original | D | 3/30/2026 | TREVORH | TREVORH | Disapproved; It appears no changes have been made,Verify Mechanical Review comments from review dated 3-12-26 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2286586 |
| Electrical | Original | D | 3/30/2026 | CONNERM | CONNERM | Comply with comments from 3/12/26 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2286106 |
| Electronic Plan | Original | / | 3/30/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2286091 |
| Zoning/Planning | Original | / | 3/30/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2286036 |
| Plumbing | Original | D | 3/30/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See highlighted sections on clouded additional requirements for 2021 IECC block. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. ST-5 is for residential use only per manufacturer. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2286030 |
| Construction | Original | D | 3/28/2026 | DOUGC | DOUGC | Architectural and Structural * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2286019 |
| Energy | Original | / | 3/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2286018 |
| Enumeration | Original | A | 3/26/2026 | BRENT | BRENT | | | Enumeration | 2285092 |
| Electronic Plan | Original | / | 3/26/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2285088 |
| Submittal 2 | Original | / | 3/26/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2284936 |
| CO Springs Fire | Original | D | 3/24/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2284110 |
| CO Springs Hazmat | Original | N | 3/24/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2284108 |
| CO Springs DRE | Original | D | 3/16/2026 | SSADLER | SSADLER | Add the legal description to the code study form. | | CO Springs DRE | 2280419 |
| Energy | Original | D | 3/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2279584 |
| Mechanical | Original | D | 3/12/2026 | TREVORH | TREVORH | Disapproved; Need to provide the MECHANICAL Com CheckNeed to see construction review comments addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2279583 |
| CSU Water | Original | N | 3/12/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 2279505 |
| CSU Waste Water | Original | N | 3/12/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 2279504 |
| Zoning/Planning | Original | / | 3/12/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2279430 |
| Electrical | Original | D | 3/12/2026 | CONNERM | CONNERM | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Comply with 250.122 (G) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2279414 |
| Electronic Plan | Original | / | 3/12/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2279390 |
| Plumbing | Original | D | 3/12/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See highlighted sections on clouded additional requirements for 2021 IECC block. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. ST-5 is for residential use only per manufacturer. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2279347 |
| Construction | Original | D | 3/12/2026 | DOUGC | DOUGC | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2279341 |
| Electronic Plan | Original | / | 3/9/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2277628 |
| Enumeration | Original | D | 2/23/2026 | BRENT | BRENT | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2269774 |
| Electronic Plan | Original | / | 2/23/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2269720 |
| | Original | / | 2/23/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/23/2026 for plan submitted 02/17/2026. Submit Date updated to now. Plan now open for review. | | | 2269583 |
| Energy | Original | / | 2/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2267249 |
| Floodplain | Original | N | 2/17/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418324045) | | Floodplain | 2267248 |