| Electrical | Original | D | 4/7/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2289864 |
| CO Springs Fire | Original | D | 4/6/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2289188 |
| CO Springs Hazmat | Original | D | 4/6/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2289187 |
| Mechanical | Original | D | 4/2/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2288024 |
| CSU Water | Original | D | 4/1/2026 | CSUREVIEW | CSUREVIEW | See previous comments.
Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.***
After approval of the CWMSF form, upload to PPRBD portal. MDA | malcuran | CSU Water | 2287861 |
| CO Springs DRE | Original | A | 4/1/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2287810 |
| Zoning/Planning | Original | / | 4/1/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2287781 |
| Plumbing | Original | D | 4/1/2026 | SHANEN | SHANEN | Provide separate DWV and water distribution isometric drawings for clarity. Provide sizing throughout and show compliance with sections 604 and 706. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2287770 |
| Construction | Original | D | 4/1/2026 | SHELLEY | SHELLEY | Previously disapproved set submitted. Ambulatory stall still not addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2287741 |
| Enumeration | Original | A | 4/1/2026 | BECKYA | BECKYA | Enumerations approved page is page 20 out of 37. | | Enumeration | 2287430 |
| | Original | / | 4/1/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2287409 |
| | Original | / | 4/1/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2287401 |
| Submittal 3 | Original | / | 4/1/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2287399 |
| Electrical | Original | D | 3/30/2026 | DANIELG | DANIELG | Pending peer review. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2286131 |
| Mechanical | Original | D | 3/27/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2285569 |
| CO Springs DRE | Original | A | 3/27/2026 | SSADLER | SSADLER | Previous approval comments still apply. Proposed changes to landscaping are minimal and will not require a modification. There will be a landscaping inspection required to check on disturbance area corrections. | | CO Springs DRE | 2285555 |
| CO Springs Hazmat | Original | D | 3/26/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2285091 |
| CO Springs Fire | Original | D | 3/26/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2285089 |
| CSU Waste Water | Original | N | 3/25/2026 | CSUREVIEW | CSUREVIEW | Currently proposed scope does not include changes to the exterior service, so previous CSU comments have been addressed. No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2284574 |
| CSU Water | Original | D | 3/25/2026 | CSUREVIEW | CSUREVIEW | Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.***
PSD | PDosch | CSU Water | 2284577 |
| Electronic Plan | Original | / | 3/25/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2284532 |
| Plumbing | Original | D | 3/25/2026 | SHANEN | SHANEN | Provide plumbing plans that are separate from the mechanical plans. Provide separate DWV and water distribution isometric drawings for clarity. Provide sizing throughout and show compliance with sections 604 and 706. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2284494 |
| Zoning/Planning | Original | / | 3/25/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2284410 |
| Construction | Original | D | 3/25/2026 | SHELLEY | SHELLEY | Ambulatory restroom stall not addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2284401 |
| Enumeration | Original | A | 3/23/2026 | BECKYA | BECKYA | | | Enumeration | 2283490 |
| Submittal 2 | Original | / | 3/23/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2283482 |
| Mechanical | Original | D | 2/27/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2274196 |
| Electronic Plan | Original | / | 2/26/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2273802 |
| CO Springs DRE | Original | A | 2/26/2026 | SSADLER | SSADLER | Approved for a commercial interior remodel. No changes to footprint, parking, or landscaping. | | CO Springs DRE | 2272301 |
| CO Springs Fire | Original | D | 2/25/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2270867 |
| CO Springs Hazmat | Original | D | 2/25/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2270866 |
| Zoning/Planning | Original | / | 2/24/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2270579 |
| Electrical | Original | D | 2/24/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2270552 |
| Electronic Plan | Original | / | 2/24/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2270484 |
| CSU Water | Original | D | 2/24/2026 | CSUREVIEW | CSUREVIEW | Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.*** PSD | PDosch | CSU Water | 2270477 |
| CSU Waste Water | Original | D | 2/24/2026 | CSUREVIEW | CSUREVIEW | A Utility Service Plan will be required for this project. Contact Utilities Development Services at (719) 668-8259 to discuss requirements. PSD | PDosch | CSU Waste Water | 2270476 |
| Plumbing | Original | D | 2/24/2026 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Remove all references to the new manhole from the plumbing plans as it will be reviewed by CSU Waste Water Department on the civil plans or USP and not by PPRBD plumbing. Provide DWV and water distribution isometric drawings for the back to back restrooms. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2270472 |
| Construction | Original | D | 2/24/2026 | SHELLEY | SHELLEY | PRELIMINARY REVIEW - too many items. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2270433 |
| Energy | Original | N | 2/24/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2270423 |
| Electronic Plan | Original | / | 2/23/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2269667 |
| Enumeration | Original | D | 2/23/2026 | BECKYA | BECKYA | The project description on the Code Study Form indicates the work is in suites 280, we do not have permit history for that suite number. The floor plan shows the scope is for suite 250. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2269524 |
| Electronic Plan | Original | / | 2/23/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2269509 |
| | Original | / | 2/23/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/23/2026 for plan submitted 02/20/2026. Submit Date updated to now. Plan now open for review. | | | 2269450 |
| Energy | Original | / | 2/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2268846 |
| Floodplain | Original | N | 2/20/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7322402001) | | Floodplain | 2268845 |