| Mechanical | Original | D | 4/30/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2301257 |
| Electrical | Original | A | 4/30/2026 | BERTHA | BERTHA | | | Electrical | 2301227 |
| Zoning/Planning | Original | / | 4/30/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2301049 |
| Construction | Original | D | 4/30/2026 | BRIANB | BRIANB | See Sheet A2.00 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2300957 |
| Electronic Plan | Original | / | 4/30/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2300940 |
| Plumbing | Original | D | 4/28/2026 | SHANEN | SHANEN | ST-5 is for residential use only per manufacturer. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2300164 |
| Enumeration | Original | A | 4/24/2026 | BECKYA | BECKYA | | | Enumeration | 2298691 |
| Submittal 2 | Original | / | 4/24/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2298627 |
| EPC Health Dept | Original | N | 3/20/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable. Offices and breakroom only. AB | abrannon | EPC Health Dept | 2282761 |
| City Engr | Original | N | 3/20/2026 | HVO | HVO | | | City Engr | 2282651 |
| CO Springs DRE | Original | A | 3/20/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No exterior changes | | CO Springs DRE | 2282525 |
| CO Springs Fire | Original | A | 3/19/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2282377 |
| CO Springs Hazmat | Original | N | 3/19/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2282375 |
| Mechanical | Original | D | 3/19/2026 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2282300 |
| Electronic Plan | Original | / | 3/19/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2282192 |
| CSU Contract Admin. | Original | N | 3/19/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due this plan set. BS | bschifferstein | CSU Contract Admin. | 2282177 |
| CSU Water | Original | N | 3/19/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2282101 |
| CSU Waste Water | Original | N | 3/19/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2282100 |
| Gas/Elec. Utils | Original | A | 3/19/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2282096 |
| Zoning/Planning | Original | / | 3/19/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2282055 |
| Electrical | Original | D | 3/19/2026 | BERTHA | BERTHA | Verify compliance with 240.24(B)
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2282039 |
| Plumbing | Original | D | 3/19/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. ST-8 is for residential use only per manufacturer. Provide an isometric drawing of the water distribution system. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2281987 |
| Electronic Plan | Original | / | 3/19/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2281967 |
| Elevators | Original | N | 3/19/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2281965 |
| Construction | Original | D | 3/19/2026 | BRIANB | BRIANB | See sheet A2.00 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2281930 |
| Energy | Original | N | 3/19/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2281929 |
| Electronic Plan | Original | / | 3/18/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2281446 |
| Enumeration | Original | A | 3/17/2026 | BECKYA | BECKYA | | | Enumeration | 2281407 |
| | Original | / | 3/17/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/17/2026 for plan submitted 02/26/2026. Submit Date updated to now. Plan now open for review. | | | 2281104 |
| Energy | Original | / | 2/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2273514 |
| Floodplain | Original | N | 2/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5505001009) | | Floodplain | 2273513 |