| Energy | Original | D | 6/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2320948 |
| Electrical | Original | D | 6/15/2026 | CONNERM | CONNERM | Panel schedules show 250A main breaker. Please clarify. Series rated info okay.
Conductors and ground undersized. Comply with 310.16 and 250.122 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2320947 |
| | Original | / | 6/11/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2319737 |
| | Original | / | 6/11/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2319728 |
| Submittal 3 | Original | / | 6/11/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2319727 |
| Monument Zoning | Original | D | 5/20/2026 | TOWNOFMON | TOWNOFMON | This project has not completed review with the Monument Planning Department. Once review is complete, Planning will provide an approval. | Rey Medina | Monument Zoning | 2310164 |
| Energy | Original | D | 5/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2310067 |
| Mechanical | Original | A | 5/20/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2310066 |
| Electrical | Original | D | 5/8/2026 | CONNERM | CONNERM | Provide series listed series combination
Provide withstand rating for RTU-2 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2304899 |
| Plumbing | Original | A | 5/5/2026 | SHANEN | SHANEN | | | Plumbing | 2303206 |
| Monument Hazmat | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Monument Hazmat | 2302919 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines.Deferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation.Field Verification Approved plans are subject to field verification. Installations not in accordance with approved plans or applicable codes may require correction.Inspection Scheduling All inspections shall be requested a minimum of 48 hours in advance through Monument Fire. Contact permits@monumentfire.org Approval by Monument Fire does not relieve the applicant from compliance with all other applicable codes, ordinances, and requirements from other agencies having jurisdiction. | SBenson9 | Monument Fire | 2302915 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | Inspection Scheduling All inspections shall be requested a minimum of 48 hours in advance through Monument Fire. Contact permits@monumentfire.org Approval by Monument Fire does not relieve the applicant from compliance with all other applicable codes, ordinances, and requirements from other agencies having jurisdiction. | SBenson9 | Monument Fire | 2302913 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | Field Verification Approved plans are subject to field verification. Installations not in accordance with approved plans or applicable codes may require correction. | SBenson9 | Monument Fire | 2302910 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | Deferred Submittals Fire protection systems shall be submitted as deferred submittals and require separate review and approval prior to installation. | SBenson9 | Monument Fire | 2302906 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | Permit Requirement Separate fire permits are required for all fire protection systems, including but not limited to fire sprinkler, fire alarm, hood suppression, standpipe, and special hazard systems. | SBenson9 | Monument Fire | 2302903 |
| Monument Fire | Original | A | 5/5/2026 | MONUMENTFIRE | MONUMENTFIRE | This review is based on the 2021 International Fire Code (IFC), as adopted and amended by Monument Fire District, including all applicable policies and standards. This review is limited to fire and life safety considerations and does not constitute approval of structural, electrical, plumbing, or other disciplines. | SBenson9 | Monument Fire | 2302901 |
| Electronic Plan | Original | / | 5/4/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2302477 |
| Construction | Original | A | 5/4/2026 | JUSTINL | JUSTINL | | | Construction | 2302452 |
| Electronic Plan | Original | / | 5/4/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2302424 |
| Enumeration | Original | A | 4/27/2026 | BECKYA | BECKYA | | | Enumeration | 2299506 |
| Submittal 2 | Original | / | 4/27/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2299480 |
| Monument Waste Water | Original | A | 4/13/2026 | MONUMENTSAN | MONUMENTSAN | Proof needs to be submitted that the 1500 grease intercepter has or will be cleaned entirely prior to opening. | parker@msan.co | Monument Waste Water | 2291874 |
| Monument Water | Original | A | 4/10/2026 | TOWNOFMON | TOWNOFMON | | jrigaud@tomgov.org | Monument Water | 2291371 |
| Tri-Lakes Fire (CSFD) | Original | D | 4/8/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Tri-Lakes Fire (CSFD) | 2290777 |
| Tri-Lakes Hazmat (CSFD) | Original | D | 4/8/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | Tri-Lakes Hazmat (CSFD) | 2290776 |
| Energy | Original | D | 3/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2287105 |
| Mechanical | Original | D | 3/31/2026 | TCRIPPEN | TCRIPPEN | Disapproved: Provide manufacturers hood sheets for type one hood * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2287104 |
| EPC Health Dept | Original | A | 3/27/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AM | Amanda Furno | EPC Health Dept | 2285763 |
| Monument Zoning | Original | D | 3/25/2026 | TOWNOFMON | TOWNOFMON | Outside lighting, trash enclosure, any changes being made to the Lot or property outside of the building structure needs review by the Monument Planning Department/Engineers. Please contact us at Planning@tomgov.org or speak to our office 719-884-8015. | bholtztom | Monument Zoning | 2284437 |
| Electrical | Original | D | 3/24/2026 | CONNERM | CONNERM | Provide one-line diagram for electrical scope of work
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
Provide fault current information (SCCR, AIC, SCA) at all of the following locations 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2283726 |
| Electronic Plan | Original | / | 3/24/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2283688 |
| EPC Health Dept | Original | D | 3/24/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2283656 |
| Plumbing | Original | D | 3/24/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to the mechanical scope from the plumbing plans. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Lavatories must show compliance with 2021 IECC section C404.5.1. All mechanical equipment condensate piping related items shall be on the mechanical plans. Remove all references to mechanical equipment condensate piping from the plumbing plans. All fixtures must discharge to the sanitary sewer. ST-12 is for residential use only per manufacturer. Provide code section that supports discharging a floor drain to a dry well. All gas piping and condensate piping related items shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2283628 |
| Construction | Original | D | 3/23/2026 | JUSTINL | JUSTINL | See architectural plans and life safety plan for review comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2283517 |
| Energy | Original | / | 3/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2282332 |
| Electronic Plan | Original | / | 3/19/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2282178 |
| Enumeration | Original | A | 2/27/2026 | BECKYA | BECKYA | 1 plan, 2 permits. Separate address assigned to Trash Enclosure. Original trash enclosure was under 7', expanded trash enclosure is over 7' | | Enumeration | 2274414 |
| Electronic Plan | Original | / | 2/27/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2274391 |
| | Original | / | 2/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/27/2026 for plan submitted 02/27/2026. Submit Date updated to now. Plan now open for review. | | | 2274282 |
| Waste Water Div | Original | / | 2/27/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2274252 |
| Energy | Original | / | 2/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2274251 |
| Floodplain | Original | N | 2/27/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7114201010) | | Floodplain | 2274250 |