| CO Springs Fire | Original | D | 4/2/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2288364 |
| CO Springs Hazmat | Original | N | 4/2/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2288358 |
| Plumbing | Original | A | 4/1/2026 | SHANEN | SHANEN | | | Plumbing | 2287814 |
| CO Springs DRE | Original | A | 4/1/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2287791 |
| Mechanical | Original | D | 4/1/2026 | TREVORH | TREVORH | disapproved; pending construction and enumeration review comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2287720 |
| Electrical | Original | D | 4/1/2026 | CONNERM | CONNERM | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2287611 |
| Electronic Plan | Original | / | 4/1/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2287515 |
| Zoning/Planning | Original | / | 4/1/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2287395 |
| CSU Water | Original | N | 4/1/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2287357 |
| CSU Waste Water | Original | N | 4/1/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2287355 |
| Construction | Original | D | 4/1/2026 | BRIANB | BRIANB | See code study form / sheets A0 / A1 / A2 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2287336 |
| Energy | Original | N | 3/30/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2286430 |
| Electronic Plan | Original | / | 3/30/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2286422 |
| Enumeration | Original | D | 3/13/2026 | BECKYA | BECKYA | The suite number for this space should be 350. Suite 315 was never an established suite number with a Certificate of Occupancy, please remove 315 from the address on all plan pages showing the address. Provide a full floor plan of the third floor with current separation of spaces and suite numbers. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2279994 |
| Electronic Plan | Original | / | 3/13/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2279937 |
| | Original | / | 3/12/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/12/2026 for plan submitted 03/12/2026. Submit Date updated to now. Plan now open for review. | | | 2279654 |
| Energy | Original | / | 3/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2278979 |
| Floodplain | Original | N | 3/12/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6432202044) | | Floodplain | 2278978 |