| Energy | Original | A | 4/8/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2290841 |
| Construction | Original | A | 4/8/2026 | DOUGC | DOUGC | | | Construction | 2290840 |
| Enumeration | Original | A | 4/8/2026 | AMY | AMY | | | Enumeration | 2290684 |
| Electronic Plan | Original | / | 4/8/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2290677 |
| | Original | / | 4/8/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2290336 |
| | Original | / | 4/8/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2290250 |
| Submittal 3 | Original | / | 4/8/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2290249 |
| Energy | Original | D | 4/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2289956 |
| Electrical | Original | A | 4/7/2026 | CONNERM | CONNERM | | | Electrical | 2289955 |
| Electronic Plan | Original | / | 4/7/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2289945 |
| Construction | Original | D | 4/7/2026 | DOUGC | DOUGC | Existing walls // Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2289934 |
| Enumeration | Original | A | 4/6/2026 | AMY | AMY | | | Enumeration | 2289358 |
| Electronic Plan | Original | / | 4/6/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2289323 |
| Submittal 2 | Original | / | 4/6/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2289216 |
| Energy | Original | D | 4/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2288408 |
| Construction | Original | D | 4/2/2026 | DOUGC | DOUGC | Architecturals * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2288407 |
| CSU Water | Original | N | 4/1/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2287676 |
| CSU Waste Water | Original | N | 4/1/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2287675 |
| Electrical | Original | D | 4/1/2026 | CONNERM | CONNERM | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2287662 |
| Plumbing | Original | N | 4/1/2026 | TCRIPPEN | TCRIPPEN | No pluming | | Plumbing | 2287530 |
| Mechanical | Original | A | 4/1/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2287528 |
| Electronic Plan | Original | / | 4/1/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2287508 |
| CO Springs Hazmat | Original | N | 3/24/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2284057 |
| CO Springs Fire | Original | A | 3/24/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | phil.valdez | CO Springs Fire | 2284054 |
| Enumeration | Original | A | 3/24/2026 | AMY | AMY | Spoke with Jazmin. Suite 110 | | Enumeration | 2283705 |
| Electronic Plan | Original | / | 3/24/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2283639 |
| Enumeration | Original | D | 3/12/2026 | AMY | AMY | The parcel numbers included on the Code Study form are from a building off of Hwy 105. Correct the parcel number. If this is an existing tenant the suite number should be suite 100. Suite 110 does not exist and does not have a certificate of occupancy (CO) and is required. If this is suite 110 this plan needs to be an interior finish. Correct the pages of this plan to suite 110, correct the Code Study form to an interior finish to receive a CO. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2279392 |
| Electronic Plan | Original | / | 3/12/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2279378 |
| | Original | / | 3/12/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/12/2026 for plan submitted 03/12/2026. Submit Date updated to now. Plan now open for review. | | | 2279165 |
| Energy | Original | / | 3/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2279065 |
| Floodplain | Original | N | 3/12/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6206403119) | | Floodplain | 2279062 |