| CSU Contract Admin. | Original | A | 4/29/2026 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees paid 4/29/2026 JMD | jdemello | CSU Contract Admin. | 2300589 |
| CSU Contract Admin. | Original | / | 4/29/2026 | CSUAPPSPRM | CSUAPPSPRM | | jdemello | CSU Contract Admin. | 2300588 |
| CO Springs Fire | Original | D | 4/21/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2297108 |
| CO Springs Hazmat | Original | N | 4/21/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2297106 |
| Energy | Original | D | 4/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2291218 |
| Electrical | Original | D | 4/9/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2291217 |
| Electronic Plan | Original | / | 4/9/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2291176 |
| Mechanical | Original | D | 4/8/2026 | TREVORH | TREVORH | Disapproved; Need to schedule walk in cooler/freezer condensers, show condensers on Roof plan if applicable.show condensate drain lines size,material and point of disposal .Provide Refrigeration calculations for the walk in cooler/Freezer or show sensors and alarms . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2290513 |
| Plumbing | Original | D | 4/8/2026 | SHANEN | SHANEN | Construction review comments must be addressed to verify occupant load.Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans.Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc.Show compliance with commercial plumbing plan review additional requirements for 2021 IECC.All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans.Ball test does not comply with section 312.CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, grease interceptor location, etc.Provide overflow scupper opening dimensions.Provide gpm and/or square footage served by each component of the roof drainage system.ST-5 is for residential use only per manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2290266 |
| Electronic Plan | Original | / | 4/8/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2290164 |
| Elevators | Original | N | 4/7/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2290157 |
| CO Springs DRE | Original | D | 4/3/2026 | SSADLER | SSADLER | Upload the final recorded plat. CDI fees are due. Contact Charla at charla.hudspeth@coloradosprings.gov
DP and final landscaping and irrigation plans are on file and stamped; Due to a policy change, assurances for private improvements are now due at the time of CO | | CO Springs DRE | 2288484 |
| CSU Contract Admin. | Original | D | 4/3/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. JMD | jdemello | CSU Contract Admin. | 2288471 |
| EPC Health Dept | Original | D | 4/2/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | EPC Health Dept | 2288447 |
| CSU Water | Original | D | 4/2/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. PSD | PDosch | CSU Water | 2288445 |
| CSU Waste Water | Original | D | 4/2/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. PSD | PDosch | CSU Waste Water | 2288444 |
| Gas/Elec. Utils | Original | A | 4/2/2026 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | Gas/Elec. Utils | 2288443 |
| Zoning/Planning | Original | / | 4/2/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2288420 |
| City Engr | Original | D | 4/2/2026 | HVO | HVO | Please include a copy of the approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2288419 |
| Construction | Original | D | 4/2/2026 | DOUGC | DOUGC | Occ Load // AAccessibility // IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2288397 |
| Electronic Plan | Original | / | 4/2/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2288288 |
| Enumeration | Original | A | 3/12/2026 | BRENT | BRENT | | | Enumeration | 2279574 |
| Electronic Plan | Original | / | 3/12/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2279548 |
| | Original | / | 3/12/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/12/2026 for plan submitted 03/12/2026. Submit Date updated to now. Plan now open for review. | | | 2279262 |
| Energy | Original | / | 3/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2279187 |
| Floodplain | Original | N | 3/12/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5304301122) | | Floodplain | 2279186 |