| CO Springs Fire | Original | N | 4/30/2026 | CSFIRE | CSFIRE | No Fire Final | Jacob.Watson | CO Springs Fire | 2300858 |
| CO Springs Hazmat | Original | N | 4/30/2026 | CSFIRE | CSFIRE | No Fire Final | Jacob.Watson | CO Springs Hazmat | 2300857 |
| Mechanical | Original | D | 4/16/2026 | TREVORH | TREVORH | Disapproved; show condensate drain line on plans include material, size and point of disposal .provide a Refrigeration calculation * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2294041 |
| CO Springs DRE | Original | A | 4/15/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2293717 |
| CSU Water | Original | N | 4/14/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2292546 |
| CSU Waste Water | Original | N | 4/14/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2292544 |
| Plumbing | Original | N | 4/13/2026 | SHANEN | SHANEN | No plumbing scope indicated. | | Plumbing | 2292214 |
| Zoning/Planning | Original | / | 4/13/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2292181 |
| Electrical | Original | D | 4/13/2026 | CONNERM | CONNERM | Provide electrical one-line diagram for scope of work
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2292162 |
| Electronic Plan | Original | / | 4/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2292138 |
| Construction | Original | D | 4/13/2026 | BPHILLIPS | BPHILLIPS | LSP, codes * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2292137 |
| Energy | Original | N | 4/13/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2292001 |
| Electronic Plan | Original | / | 4/13/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2291899 |
| Enumeration | Original | D | 3/19/2026 | AMY | AMY | The permit history on this building is 7years old. Please provide a floor plan showing the separation of space per tenant along with the unit number. What unit number is the Wag n Wash? Add the unit number to the Code Study form as well. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2281885 |
| Electronic Plan | Original | / | 3/19/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2281882 |
| | Original | / | 3/18/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/18/2026 for plan submitted 03/17/2026. Submit Date updated to now. Plan now open for review. | | | 2281698 |
| Energy | Original | / | 3/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2281064 |
| Floodplain | Original | N | 3/17/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308019062) | | Floodplain | 2281063 |