| CO Springs DRE | Original | D | 5/14/2026 | SSADLER | SSADLER | Previous comments not addressed. Contact the case planner to obtain and upload the pre application summary | | CO Springs DRE | 2307721 |
| EPC Health Dept | Original | D | 5/12/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2306371 |
| Electrical | Original | A | 5/11/2026 | DANIELG | DANIELG | | | Electrical | 2305876 |
| Mechanical | Original | D | 5/11/2026 | TREVORH | TREVORH | Disapproved; Still Need to see Construction Review comments Addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2305857 |
| CSU Waste Water | Original | A | 5/11/2026 | CSUREVIEW | CSUREVIEW | Comments addressed. SSH | SHillman | CSU Waste Water | 2305651 |
| Zoning/Planning | Original | / | 5/11/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2305611 |
| Plumbing | Original | D | 5/11/2026 | SHANEN | SHANEN | Construction review comments regarding restroom accessibility must be addressed. Table E201.1 does not exist in 21 IPC appendix E. Reference table E104.1. Provide required CSU variance letter for the indoor grease trap. Contact Robert Bowren at 719-668-1735 or fog@csu.org. CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2305593 |
| Construction | Original | D | 5/11/2026 | SHELLEY | SHELLEY | See LSP, code study form, and floor plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2305584 |
| Submittal 2 | Original | / | 5/7/2026 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2304656 |
| CO Springs Fire | Original | D | 4/21/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2297059 |
| CO Springs Hazmat | Original | D | 4/21/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2297056 |
| CO Springs DRE | Original | D | 4/21/2026 | SSADLER | SSADLER | Contact case planner to obtain pre application summary. | | CO Springs DRE | 2295629 |
| EPC Health Dept | Original | D | 4/17/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2294718 |
| Mechanical | Original | D | 4/17/2026 | TREVORH | TREVORH | Disapproved; Need to see construction review comments addressed regarding occupancy and lack of Rest rooms * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2294619 |
| CSU Water | Original | N | 4/16/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2294284 |
| CSU Waste Water | Original | D | 4/16/2026 | CSUREVIEW | CSUREVIEW | The grease interceptor sizing form provided on P0.1 is an old version of the form. Please fill out and upload a new copy of the form, found at this link: https://www.csu.org/hubfs/Document-Library/GreaseInterceptorSizingForm.pdf?csf=1&e=PJyGju
Please provide the size and location of the grease interceptor that will be used to collect all the waste from the fixtures that are listed on the GI form.
If any grease interceptors outside the building are getting demolished/abandoned/altered, you will need to submit a Utility Service Plan to Colorado Springs Utilities for review and approval.
Call UDS at 719-668-8259 with questions. SSH | SHillman | CSU Waste Water | 2294278 |
| Electrical | Original | A | 4/16/2026 | DANIELG | DANIELG | | | Electrical | 2294084 |
| Plumbing | Original | D | 4/16/2026 | SHANEN | SHANEN | Construction review comments regarding occupancy and restroom access must be addressed. Table E201.1 does not exist in 21 IPC appendix E. Reference table E104.1. Provide required CSU variance letter for the indoor grease trap. Contact Robert Bowren at 719-668-1735 or fog@csu.org. CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2294079 |
| Zoning/Planning | Original | / | 4/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2294072 |
| Electronic Plan | Original | / | 4/16/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2294051 |
| Construction | Original | D | 4/16/2026 | SHELLEY | SHELLEY | See plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2294037 |
| Energy | Original | N | 4/15/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2293344 |
| Electronic Plan | Original | / | 4/15/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2293178 |
| Construction | Original | / | 4/10/2026 | QUINTONW | QUINTONW | Overtime approved for Construction by Approved Per Randy | | Construction | 2291483 |
| Floodplain | Original | N | 3/24/2026 | AMY | AMY | | | Floodplain | 2283787 |
| Enumeration | Original | N | 3/24/2026 | AMY | AMY | | | Enumeration | 2283786 |
| Electronic Plan | Original | / | 3/24/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2283767 |
| | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/24/2026 for plan submitted 03/23/2026. Submit Date updated to now. Plan now open for review. | | | 2283677 |
| Energy | Original | / | 3/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2282964 |
| Floodplain | Original | / | 3/23/2026 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 6418207027) | | Floodplain | 2282963 |