| Energy | Original | D | 4/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2298394 |
| Mechanical | Original | D | 4/23/2026 | TREVORH | TREVORH | Disapproved; Provide Combustion Air calculation * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2298393 |
| Tri-Lakes Hazmat (CSFD) | Original | N | 4/21/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Tri-Lakes Hazmat (CSFD) | 2295625 |
| Tri-Lakes Fire (CSFD) | Original | A | 4/21/2026 | MONUMENTFIRE | MONUMENTFIRE | Monument Fire District – Plan Review Comments
All fire and life safety systems, features, and operations shall comply with the currently adopted 2021 International Fire Code (IFC) and all locally adopted amendments as enforced by Monument Fire District.
Permitting: All required fire permits shall be submitted online at: www.monumentfire.org/permits
Inspections: All inspections shall be scheduled a minimum of 48 hours in advance. Inspection requests may be made by contacting the assigned plan reviewer or by emailing: Permits@monumentfire.org
General Inquiries: For questions regarding permits, inspections, or plan review comments, contact: Permits@monumentfire.org | SBenson9 | Tri-Lakes Fire (CSFD) | 2295624 |
| Tri-Lakes Fire (CSFD) | Original | A | 4/21/2026 | MONUMENTFIRE | MONUMENTFIRE | Monument Fire District – Plan Review Comments
All fire and life safety systems, features, and operations shall comply with the currently adopted 2021 International Fire Code (IFC) and all locally adopted amendments as enforced by Monument Fire District.
Permitting: All required fire permits shall be submitted online at: www.monumentfire.org/permits
Inspections: All inspections shall be scheduled a minimum of 48 hours in advance. Inspection requests may be made by contacting the assigned plan reviewer or by emailing: Permits@monumentfire.org
General Inquiries: For questions regarding permits, inspections, or plan review comments, contact: Permits@monumentfire.org | SBenson9 | Tri-Lakes Fire (CSFD) | 2295623 |
| Energy | Original | / | 4/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2294919 |
| Construction | Original | D | 4/18/2026 | DOUGC | DOUGC | CSF // Life Safety // Occupancy * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2294918 |
| Electronic Plan | Original | / | 4/15/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2293598 |
| Plumbing | Original | D | 4/8/2026 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1.Change of occupancy requires compliance with section 403.1. Provide, schedule, locate and show piping for the required drinking fountain. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2290553 |
| Electrical | Original | A | 4/8/2026 | CONNERM | CONNERM | | | Electrical | 2290507 |
| Electronic Plan | Original | / | 3/24/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2283797 |
| | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/24/2026 for plan submitted 03/24/2026. Submit Date updated to now. Plan now open for review. | | | 2283665 |
| Waste Water Div | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2283661 |
| Energy | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2283660 |
| Floodplain | Original | N | 3/24/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7115211003) | | Floodplain | 2283657 |