| Monument Zoning | Original | D | 5/18/2026 | TOWNOFMON | TOWNOFMON | | Rey Medina | Monument Zoning | 2308624 |
| Monument Zoning | Original | / | 5/18/2026 | TOWNOFMON | TOWNOFMON | | Rey Medina | Monument Zoning | 2308623 |
| Monument Zoning | Original | A | 5/18/2026 | TOWNOFMON | TOWNOFMON | | Rey Medina | Monument Zoning | 2308600 |
| Triview Water | Original | D | 4/23/2026 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Please update the civil plans to match the approved plan set dated 3/12/26. 2. Please replace water service details 1/P500 and 3/P500 on sheet P500 with Colorado Springs Utilities detail B4-8 “Typical Installation for 1-1/2” thru 6” Meters.”
Please update the following on P101.1 (plumbing) to match civil drawings: 3. Retail A1, plumbing plans show indoor irrigation connection. The approved site development CDs show all irrigation meter pits set outdoors. Please remove indoor irrigation connection references. 4. Retail A1, plumbing plans show a 1.5” DCW with 1.5” meter but civil plans show a 2” DCW with 1.5” meter. 5. Retail A1, plumbing plans show a 4” fire service line but civil plans show an 8” DI fire service. 6. Marshalls/Homegoods, plumbing plans show a 4” fire service line but civil plans show an 8” DI fire service. 7. Dining B-5 plumbing plans show a 4” fire service line but civil plans show a 6” DI fire service line. | rnortonTMD | Triview Water | 2298274 |
| Triview Water | Original | D | 4/23/2026 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Please update the civil plans to match the approved plan set dated 3/12/26. 2. Please replace water service details 1/P500 and 3/P500 on sheet P500 with Colorado Springs Utilities detail B4-8 “Typical Installation for 1-1/2” thru 6” Meters.”
Please update the following on P101.1 to match civil drawings: 3. Retail A1, plumbing plans show an indoor irrigation connection. According to the approved site development construction drawings, all irrigation is planned to be serviced by outdoor irrigation meter pits. Please remove indoor irrigation connection references. 4. For Retail A1, plumbing plans show a 1.5” DCW with 1.5” meter but civil plans show a 2” DCW with 1.5” meter. 5. Retail A1, plumbing plans show a 4” fire service line but civil plans show an 8” DI fire service. 6. Marshalls and Homegoods, plumbing plans show a 4” fire service line but civil plans show an 8” DI fire service. 7. Dining B-5, plumbing plans show a 4” fire service line but civil plans show | rnortonTMD | Triview Water | 2298280 |
| Triview Waste Water | Original | A | 4/23/2026 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Waste Water | 2298247 |
| Mechanical | Original | D | 4/20/2026 | TREVORH | TREVORH | Disapproved; Need city Gas/utilities comments addressed, Need to see construction review comments addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2295025 |
| Energy | Original | D | 4/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2295026 |
| Electrical | Original | D | 4/17/2026 | BERTHA | BERTHA | Pending Enumeration approval - Multi-meter services must include a list of enumerated addresses on the one-line diagram
Provide all conductor size, type and quantity
Verify rating of panels
Comply with 210.25(B)
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Footprint (site plan) showing all electrical service equipment and disconnects serving the structure - for example 1000A MDPs
Provide all panel schedules - 1000A MDPs
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2294916 |
| Tri-Lakes Hazmat (CSFD) | Original | N | 4/17/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Tri-Lakes Hazmat (CSFD) | 2294616 |
| Tri-Lakes Fire (CSFD) | Original | A | 4/17/2026 | MONUMENTFIRE | MONUMENTFIRE | Monument Fire District – Plan Review Comments
All fire and life safety systems, features, and operations shall comply with the currently adopted 2021 International Fire Code (IFC) and all locally adopted amendments as enforced by Monument Fire District.
Permitting: All required fire permits shall be submitted online at: www.monumentfire.org/permits
Inspections: All inspections shall be scheduled a minimum of 48 hours in advance. Inspection requests may be made by contacting the assigned plan reviewer or by emailing: Permits@monumentfire.org
General Inquiries: For questions regarding permits, inspections, or plan review comments, contact: Permits@monumentfire.org | SBenson9 | Tri-Lakes Fire (CSFD) | 2294613 |
| Plumbing | Original | D | 4/17/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide a piping materials schedule. Provide a two way fitting or two riser clean-out at the junction of each building drain and building sewer in compliance with CO state amendment to section 708.1.3. Show vent piping for the grease interceptor if required by manufacturer or waste water department. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2294382 |
| Gas/Elec. Utils | Original | D | 4/17/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. Not in Colorado Springs Utilities' gas service territory. SSH | SHillman | Gas/Elec. Utils | 2294379 |
| CSU Contract Admin. | Original | D | 4/16/2026 | CSUAPPSPRM | CSUAPPSPRM | Address is not within CSU service area. Please contact correct service provider.
AMS | ASweet | CSU Contract Admin. | 2294365 |
| Energy | Original | / | 4/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2294351 |
| Construction | Original | D | 4/16/2026 | SHELLEY | SHELLEY | Unlimited area issue; occupancy classification; egress width; rated construction, see plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2294348 |
| Electronic Plan | Original | / | 4/16/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2293799 |
| Electronic Plan | Original | / | 4/15/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2293474 |
| Floodplain | Original | N | 3/25/2026 | KEITH | KEITH | | | Floodplain | 2284182 |
| Enumeration | Original | D | 3/24/2026 | BECKYA | BECKYA | 1. See site plan A100 for comments regarding adding addressing. Please be sure to add trash enclosure addresses. 2. See page A101.1 for comments regarding secondary addressing. Please update this page to show proper secondary addressing. 3. Final Plat has not yet been approved by Enumerations. Once the final recorded plat for Legacy at Jackson Creek has been recorded and sent to us, we can approve this plan. Okay to email to Becky Allen (beckya@pprbd.org) 4. Enumerations will review the pre-plat (mylar) in person, prior to plat for address placement, street names, and title block. 5. A $10.00 per lot and tract platting fee will be due at the time of the review of the pre-plat, (two addresses per lot and tract). If an address is not needed on a tract then no fee applies. Check should be made out to PIKES PEAK REGIONAL BUILDING DEPARTMENT or PPRBD. As of December 5th 2023, the fee for all credit/debit cards has changed from the flat 2.95% fee to the following: Over the phone Credit/Debit Card payments will be 2.3% and In-Person Debit Card payments will be 1.5% (in-person only). Paid directly to the Enumerations Department. 6. Pre-plat reviews will need to be in-person. The pre-plat will be stamped by Enumerations for accuracy and returned to the applicant and the planner. All payments to be mailed to RBD via a check or credit card payment over the phone. Plats should not be recorded prior to Enumerations stamping the pre-plat and receiving payment of plat fees. If any pre-plat changes occur, even if changes do not apply to Enumerations, we still need to re-stamp the pre-plat. The Enumerations stamped pre-plat copy should match the recorded document minus a few signatures. If you would like an in-person review, please make an appointment on our website, https://www.pprbd.org/Home/BookAppt * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2284101 |
| Electronic Plan | Original | / | 3/24/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2284056 |
| | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/24/2026 for plan submitted 03/24/2026. Submit Date updated to now. Plan now open for review. | | | 2284015 |
| Fire | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2283992 |
| Waste Water Div | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2283993 |
| Hazmat | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2283991 |
| Energy | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2283990 |