| Monument Zoning | Original | D | 5/18/2026 | TOWNOFMON | TOWNOFMON | Monument Zoning will approve once Monument has received a Commercial New Build Permit confirming all impact fees have been paid. | Rey Medina | Monument Zoning | 2308621 |
| Monument Zoning | Original | / | 5/18/2026 | TOWNOFMON | TOWNOFMON | | Rey Medina | Monument Zoning | 2308618 |
| Monument Zoning | Original | D | 5/18/2026 | TOWNOFMON | TOWNOFMON | Plans will be approved once Monument Commercial New Build permit is acquired, confirming payment of impact fees. | Rey Medina | Monument Zoning | 2308615 |
| Monument Zoning | Original | A | 5/18/2026 | TOWNOFMON | TOWNOFMON | | Rey Medina | Monument Zoning | 2308609 |
| Triview Water | Original | D | 4/23/2026 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Please update the civil plans to match the approved plan set dated 3/12/26. 2. Please replace water service detail 3/P500 on sheet P500 with Colorado Springs Utilities detail B4-8 “Typical Installation for 1-1/2” thru 6” Meters.” 3. P101.2 (plumbing) – Plumbing plans show an indoor irrigation connection. According to the approved site development construction drawings, all irrigation is planned to be serviced by outdoor irrigation meter pits. Please remove indoor irrigation connection references. | rnortonTMD | Triview Water | 2298303 |
| Triview Waste Water | Original | A | 4/23/2026 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Waste Water | 2298301 |
| Energy | Original | D | 4/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2295284 |
| Electrical | Original | D | 4/20/2026 | BERTHA | BERTHA | Pending approval in Enumerations - Multi-meter services must include a list of enumerated addresses on the one-line diagram
Provide footprint (site plan) showing all electrical equipment
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2295283 |
| Mechanical | Original | D | 4/17/2026 | TREVORH | TREVORH | Disapproved; * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2294742 |
| Tri-Lakes Hazmat (CSFD) | Original | N | 4/17/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Tri-Lakes Hazmat (CSFD) | 2294655 |
| Tri-Lakes Fire (CSFD) | Original | A | 4/17/2026 | MONUMENTFIRE | MONUMENTFIRE | Monument Fire District – Plan Review Comments
All fire and life safety systems, features, and operations shall comply with the currently adopted 2021 International Fire Code (IFC) and all locally adopted amendments as enforced by Monument Fire District.
Permitting: All required fire permits shall be submitted online at: www.monumentfire.org/permits
Inspections: All inspections shall be scheduled a minimum of 48 hours in advance. Inspection requests may be made by contacting the assigned plan reviewer or by emailing: Permits@monumentfire.org
General Inquiries: For questions regarding permits, inspections, or plan review comments, contact: Permits@monumentfire.org | SBenson9 | Tri-Lakes Fire (CSFD) | 2294654 |
| Plumbing | Original | D | 4/17/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide a piping materials schedule. Provide a two way fitting or two riser clean-out at the junction of each building drain and building sewer in compliance with CO state amendment to section 708.1.3. Show vent piping for the grease interceptor if required by manufacturer or waste water department. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2294388 |
| Gas/Elec. Utils | Original | D | 4/17/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. Not in Colorado Springs Utilities' gas service territory. SSH | SHillman | Gas/Elec. Utils | 2294380 |
| Electronic Plan | Original | / | 4/16/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2294368 |
| CSU Contract Admin. | Original | D | 4/16/2026 | CSUAPPSPRM | CSUAPPSPRM | Address is not within CSU service area. Please contact correct service provider.
AMS | ASweet | CSU Contract Admin. | 2294364 |
| Construction | Original | D | 4/16/2026 | SHELLEY | SHELLEY | Unlimited area issue; occupancy classification; egress width; rated construction, see plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2294356 |
| Energy | Original | / | 4/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2294352 |
| Electronic Plan | Original | / | 4/16/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2293870 |
| Floodplain | Original | N | 3/25/2026 | KEITH | KEITH | | | Floodplain | 2284145 |
| Enumeration | Original | D | 3/24/2026 | AMY | AMY | Secondary addressing was readjusted to meet our standard: from west to east 140, 130, 120, 110, 100. What was applied was crossed out. The trash enclosure requires a separate address and permit. That address is 1293 Blevins Buckle Trail. Address corrected on IECC Cert. If any of these sheets get changed out, please correct the information. Approval of this plan is pending in the Enumerations department based on Enumerations needing to review the mylar prior to plat, collection of plat fees and a copy of the final recorded plat. Including the above information. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2284092 |
| Electronic Plan | Original | / | 3/24/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2284065 |
| | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/24/2026 for plan submitted 03/24/2026. Submit Date updated to now. Plan now open for review. | | | 2284014 |
| Waste Water Div | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2284003 |
| Fire | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2284002 |
| Hazmat | Original | / | 3/24/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2284001 |
| Energy | Original | / | 3/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2284000 |