| Energy | Original | D | 5/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2307165 |
| Mechanical | Original | D | 5/14/2026 | DALEH | DALEH | Provide mechanical as needed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2307164 |
| Monument Zoning | Original | D | 5/4/2026 | TOWNOFMON | TOWNOFMON | Please call Monument Planning Department at 719-884-8015 | bholtztom | Monument Zoning | 2302558 |
| Mechanical | Original | / | 4/30/2026 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by Bradley Ward | bmward79 | Mechanical | 2301073 |
| Monument Water | Original | A | 4/28/2026 | TOWNOFMON | TOWNOFMON | | jrigaud@tomgov.org | Monument Water | 2299684 |
| Mechanical | Original | / | 4/24/2026 | WEBSITE | WEBSITE | Overtime Deauthorized for Mechanical by Bradley Ward | bmward79 | Mechanical | 2298748 |
| Tri-Lakes Hazmat (CSFD) | Original | N | 4/21/2026 | MONUMENTFIRE | MONUMENTFIRE | | SBenson9 | Tri-Lakes Hazmat (CSFD) | 2297054 |
| Tri-Lakes Fire (CSFD) | Original | A | 4/21/2026 | MONUMENTFIRE | MONUMENTFIRE | Monument Fire District – Plan Review Comments
All fire and life safety systems, features, and operations shall comply with the currently adopted 2021 International Fire Code (IFC) and all locally adopted amendments as enforced by Monument Fire District.
Permitting: All required fire permits shall be submitted online at: www.monumentfire.org/permits
Inspections: All inspections shall be scheduled a minimum of 48 hours in advance. Inspection requests may be made by contacting the assigned plan reviewer or by emailing: Permits@monumentfire.org
General Inquiries: For questions regarding permits, inspections, or plan review comments, contact: Permits@monumentfire.org | SBenson9 | Tri-Lakes Fire (CSFD) | 2297052 |
| Electrical | Original | D | 4/17/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Provide panel schedule and load calc for electrical panel
Provide electrical one-line diagram
Identify electrical panel
Panel and circuit number on all electrical equipment (new and relocated)
All new and existing electrical devices must comply with ANSI 117.1 section 308 reach range * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2294727 |
| Plumbing | Original | D | 4/17/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Change of occupancy requires compliance with section 403. Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Show DWV and water distribution piping to new sinks from the point of connection and show sizing at each point of connection. Schedule new sinks and faucets with manufacturer model numbers. COPPER PIPING PRODUCTS ARE PROHIBITED IN SOME AREAS SERVED BY MONUMENT WASTE WATER DEPT. CALL 719-884-8039 FOR VERIFICATION. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2294703 |
| Electronic Plan | Original | / | 4/17/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2294700 |
| Construction | Original | D | 4/17/2026 | SHELLEY | SHELLEY | Code, LSP, occupant load, see plans for comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2294690 |
| Electronic Plan | Original | / | 4/17/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2294645 |
| Plumbing | Original | / | 4/7/2026 | WEBSITE | WEBSITE | Overtime Authorized for Plumbing by Bradley Ward | bmward79 | Plumbing | 2289671 |
| Mechanical | Original | / | 4/7/2026 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by Bradley Ward | bmward79 | Mechanical | 2289670 |
| Electrical | Original | / | 4/7/2026 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by Bradley Ward | bmward79 | Electrical | 2289666 |
| Construction | Original | / | 4/7/2026 | WEBSITE | WEBSITE | Overtime Authorized for Construction by Bradley Ward | bmward79 | Construction | 2289664 |
| Enumeration | Original | D | 3/26/2026 | BECKYA | BECKYA | Please provide an Architectural Site plan or vicinity map. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2285161 |
| Electronic Plan | Original | / | 3/26/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2285159 |
| | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/26/2026 for plan submitted 03/26/2026. Submit Date updated to now. Plan now open for review. | | | 2284890 |
| Waste Water Div | Original | / | 3/26/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2284887 |
| Energy | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2284886 |
| Floodplain | Original | N | 3/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7115404015) | | Floodplain | 2284884 |