| EPC Health Dept | Original | A | 5/14/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AB | abrannon | EPC Health Dept | 2307744 |
| Zoning/Planning | Original | / | 5/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2307452 |
| Mechanical | Original | A | 5/14/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2307404 |
| Plumbing | Original | A | 5/14/2026 | SHANEN | SHANEN | | | Plumbing | 2307397 |
| Electrical | Original | D | 5/14/2026 | CONNERM | CONNERM | Comply with IECC C405.11. Controlled receptacles must be shown on the plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2307385 |
| Electronic Plan | Original | / | 5/14/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2307372 |
| Construction | Original | A | 5/14/2026 | SHELLEY | SHELLEY | | | Construction | 2307357 |
| Submittal 2 | Original | / | 5/13/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2306883 |
| CO Springs Fire | Original | D | 4/30/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2300964 |
| CO Springs Hazmat | Original | N | 4/30/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2300962 |
| CO Springs DRE | Original | A | 4/23/2026 | SSADLER | SSADLER | Approved for proposed interior remodel and exterior patio. | | CO Springs DRE | 2298076 |
| EPC Health Dept | Original | D | 4/22/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2297546 |
| CSU Waste Water | Original | N | 4/21/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2297118 |
| CSU Water | Original | N | 4/21/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2297116 |
| Mechanical | Original | D | 4/21/2026 | TREVORH | TREVORH | Disapproved; This submittal package is missing the Natural Gas piping uplodad * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2297082 |
| Zoning/Planning | Original | / | 4/21/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2297066 |
| Electrical | Original | D | 4/21/2026 | CONNERM | CONNERM | Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Provide Fault current information (SCCR, AIC, SCA) new cooling equipment * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2297040 |
| Plumbing | Original | D | 4/21/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping and condensate piping related items shall be on the mechanical plans. Remove ALL references to gas piping and condensate piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. ST-12 is for residential use only per manufacturer. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2297029 |
| Electronic Plan | Original | / | 4/21/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2297017 |
| Construction | Original | D | 4/21/2026 | SHELLEY | SHELLEY | See LS1.1 and S1.0 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2296997 |
| Energy | Original | N | 4/21/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2296994 |
| Electronic Plan | Original | / | 4/20/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2295209 |
| Enumeration | Original | N | 3/26/2026 | BECKYA | BECKYA | | | Enumeration | 2285168 |
| Electronic Plan | Original | / | 3/26/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2285164 |
| | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/26/2026 for plan submitted 03/26/2026. Submit Date updated to now. Plan now open for review. | | | 2285156 |
| Energy | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2284896 |
| Floodplain | Original | N | 3/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6232102001) | | Floodplain | 2284895 |