| Fountain Fire | Original | D | 5/8/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Fountain Fire | 2305145 |
| Fountain Hazmat | Original | N | 5/8/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | Fountain Hazmat | 2305143 |
| Energy | Original | D | 5/7/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2304515 |
| Mechanical | Original | D | 5/7/2026 | TREVORH | TREVORH | Disapproved; Need to provide the Hood interlock sequence of operation * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2304514 |
| EPC Health Dept | Original | D | 4/22/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2297762 |
| Electrical | Original | D | 4/22/2026 | CONNERM | CONNERM | Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2297317 |
| Plumbing | Original | D | 4/22/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to other plumbing codes. See clouded sections on additional requirements for 2021 IECC block. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Show key note 7 on sanitary and vent floor plan. Show key note 18, 19, 24 and 25 on domestic water plan. ST-12 is for residential use only per manufacturer. Water heater detail must show compliance with IECC section C404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2297295 |
| Electronic Plan | Original | / | 4/22/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2297269 |
| Energy | Original | / | 4/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2297249 |
| Construction | Original | D | 4/22/2026 | DOUGC | DOUGC | Accessibility // Occ Load // Structural Design Criteria * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2297248 |
| Electronic Plan | Original | / | 4/21/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2295796 |
| Enumeration | Original | D | 3/31/2026 | BRENT | BRENT | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2287046 |
| Electronic Plan | Original | / | 3/31/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2287037 |
| | Original | / | 3/31/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/31/2026 for plan submitted 03/26/2026. Submit Date updated to now. Plan now open for review. | | | 2287028 |
| Waste Water Div | Original | / | 3/26/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2284992 |
| Water Division | Original | / | 3/26/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2284991 |
| Energy | Original | / | 3/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2284990 |
| Floodplain | Original | N | 3/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5530007001) | | Floodplain | 2284989 |